Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> C o u N T AMENDED <br /> 3/2/2022 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 7-ELEVEN INC#41341 14405 PACIFIC AVE, STOCKTON June 24, 2021 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 106 CCR 2632(d), 2641(h) Failure to submit and maintain a current facility plot plan/site map. <br /> OBSERVATION:An accurate UST Monitoring Site Plan was not submitted. One of the site maps lists the 87&91 <br /> tanks as 10,000 gallons each. Removed dispensers are still included on two of the site maps. <br /> REGULATION GUIDANCE:A site plan must be submitted identifying the locations where monitoring will be <br /> performed. The site plan must show the general layout of tanks and piping and clearly identify locations of the <br /> following equipment, if installed: 1)monitoring system control panels; 2)in-tank liquid level probes (if used for leak <br /> detection); 3)devices monitoring tank annular spaces or vault;4)devices monitoring product piping; 5)devices <br /> monitoring fill piping; 6)devices monitoring vent piping; 7)devices monitoring vapor recovery piping; 8)devices <br /> monitoring vent/transition sumps; 9)devices monitoring under-dispenser containment; 10)line leak detectors; and <br /> 11)devices monitoring any other secondary containment areas. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov/and upload a copy of the UST Monitoring Site Plan. <br /> This is a minor violation. <br /> 109 CCR 2715(a)(1)(B), 2715(a)(3) Failure to submit"Designated Underground Storage Tank Operator Identification <br /> Form"within 30 days. <br /> OBSERVATION: The Designated Underground Storage Tank Operator Identification Form was not submitted in <br /> CERS and was marked as Exempt. Facility is no longer in temporary closure as of 6/17/2021. <br /> REGULATION GUIDANCE: By January 1, 2005, owners of underground storage tank systems shall submit a <br /> signed statement to the local agency indicating that the owner understands and is in compliance with all applicable <br /> underground storage tank requirements, and identifying the designated UST operator(s)for each facility owned. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov and upload the notification identifying all the designated operators for this facility. <br /> This is a minor violation. <br /> FA0007787 PR0508452 SCO01 06/24/2021 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />