Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> Replaced Test Boots and Jumper Lines to 87, 89, 91 East, 87, 89, 91 West Secondary Piping and Diesel Secondary Piping. <br /> Retested and passed. <br /> Replaced Test Boots and Jumper Lines in UDC 1/2, 3/4, 5/6 -Retested and Failed Due to Penetration Boots. <br /> Replaced Test Boots and Jumper Lines in UDC 7/8,9/10, 11/12 -Retested and Passed. <br /> No Inspector Present. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />