Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> F1 Check this box if tank gauging is used only for inventory control. <br /> Check this box if NO tank gauging equipment is installed. Yes No NA <br /> Do not complete this section if either box is checked. <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and F 17 E <br /> termination; and 2 tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup 17 ri 0 <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? <br /> Was accuracy of system's water level readings tested? <br /> Were all probes reinstalled properly? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? r] <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> ® r <br /> 0 M <br /> El 17 <br /> El <br /> Ir❑ El <br /> 9. COMMENTS <br /> Describe all answers marked "No"or "Fail"and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> -Each sump sensor was tested twice to ensure positive shutdown to alternating 87 turbines. <br /> Positive shutdown was verified and passed. <br /> -Found L21: Unl T-1 Fill Sump Sensor defective and wires exposed. Replaced the Fill sump <br /> sensor with like for like 794380-208. All passed after sensor was replaced. <br /> Page 5 of 6 <br />