Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by ❑Manufacturer 0✓ Industry Standard ❑Professional Engineer <br />Test Type ❑Pressure ❑Vacuum ❑✓ Hydrostatic <br />Test Equipment Used: Incon TS STS. <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump/UDC ID <br />Piping Sump 1 <br />Piping Sump 2 <br />Sump Manufacturer <br />Containment <br />Containment <br />Sump Depth (inches) <br />48 <br />48 <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />19 <br />18 <br />Test Start Time <br />20:29 <br />08:29 <br />Initial Reading <br />6.3753 <br />4.6051 <br />Test End Time <br />08:44 <br />08:44 <br />Final Reading <br />6.3748 <br />4.6044 <br />❑Pass ❑Fail <br />❑Pass ❑Fail <br />Change in Reading <br />0.0005 <br />0.0007 <br />Pass/Fail Criteria <br />0.002 <br />0.002 <br />Tightness Test Results <br />❑✓ Pass ❑Fail <br />❑] Pass ❑Fail <br />❑Pass ❑Fail <br />❑Pass ❑Fail <br />Sump/UDC ID <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results <br />❑Pass ❑Fail <br />❑Pass ❑Fail <br />❑Pass ❑Fail <br />❑Pass ❑Fail <br />Additional copies of this page maybe attached. <br />All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />