Laserfiche WebLink
Tanknology <br />Work Order: 2356998 <br />Site Name/ID: Lodi / Lodi <br />Address: 2500 W Turner Road <br />City: Lodi <br />Product Line Tightness Test <br />Date: 6/10/2022 <br />State: CA Zip: 95242 <br />Page 1 of 1 <br />Tank Information <br />Tank # 1 <br />Line # 1 <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Tank # <br />Line # <br />Test Method <br />TLD -1 <br />Customer Tank ID <br />T1 <br />Product Name <br />Diesel <br />Delivery Type <br />Pressure <br />Test Pressure (psi) <br />60 <br />Test Start Time <br />09:15 <br />Test End Time <br />09:45 <br />Final Leak Rate (gph) <br />0.00 <br />Test Result(P/F/1) <br />Pass <br />Test was performed per <br />3rd party certifications as <br />specified in 40 CFR parts <br />280 and 281 <br />Yes <br />Technician Comments: <br />Technician Name: Brent Bowen <br />Technician Signature: <br />Certification M 14-1759 exp: <br />8/31/2023 <br />Environmental Compliance for Petroleum Systems <br />02022 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com <br />