Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> C C u N T AMENDED <br /> 4/28/2022 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> JAHANT FOOD N FUEL STOP 24323 N HWY 99 , ACAMPO April 28, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 210 CCR 2715(c)Failure to provide initial training,train every 12 months, and have a trained employee present. <br /> OBSERVATION: The designated operator employee training for Bachitar Singh was not performed. <br /> REGULATION GUIDANCE: The designated operator shall train facility employees in the proper operation and <br /> maintenance of the UST system at least once every 12 months. The training shall be conducted before the <br /> individual performs the duties of a facility employees.The training shall include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Initial training shall also include a site-specific practical demonstration that provides both sharing information and <br /> evaluating knowledge for responding to emergencies, leak detection, monitoring alarms, spills and overfills. At least <br /> one of the facility employees present during operating hours shall have current training. <br /> CORRECTIVE ACTION: Ensure that employees have been trained by the designated operator, maintain the list on <br /> site, and submit a copy of the training records to the EHD. <br /> This is a Class II violation. <br /> 301 HSC 25292.1(a)Failure to operate UST system to prevent unauthorized releases including leaks,spills and overfills. <br /> OBSERVATION: The following UDCs was observed with liquid: <br /> - 1-2 UDC with approximately half a cup of liquid <br /> -3-4 UDC with approximately half a cup of liquid <br /> -5-6 UDC with approximately half a cup of liquid <br /> -7-8 UDC with approximately half a cup of liquid <br /> REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br /> releases, including spills and overfills. <br /> CORRECTIVE ACTION: Immediately removed the liquid from the UDCs. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended <br /> and replaces the initial report. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the amended inspection report. <br /> ***Note <br /> FA0004345 PR0231947 SCO01 04/28/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />