Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer ❑fT Industry Standard 0 Professional Engineer <br /> Test Type © Pressure ® Vacuum E Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID Gasoline -87 Gasoline -91 Disp#1-2 Disp#3-4 <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP Bravo Bravo <br /> Sump Depth (inches) 52 54 9 9 <br /> Sump Bottom to Top of 20 20 Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:40 10:40 10:40 10:40 <br /> Initial Reading 4.2322 2.0615 3.1434 .6416 <br /> Test End Time 10:55 10:55 10:55 10:55 <br /> Final Reading 4.2304 2.0608 3.1432 .6418 <br /> Change in Reading -.0018 -.0007 -.0002 .0002 <br /> Pass/Fail Criteria .002 .002 .002 .002 <br /> Tightness Test Results © Pass rl Fail E✓ Pass rl Fail7 Pass © Fail © Pass Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass Fail Criteria <br /> Tightness Test Results Pass 0 Fail 0 Pass Fail 0 Pass [r] Fail C Pass C Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />