Laserfiche WebLink
Seismic/Anchoring: <br /> Civil engineer wet stamped seismic/dynamic/hydrostatic load calculations provided <br /> as Attachment "D". The tank will not slide or overturn during a seismic event. <br /> Seismic/Anchoring findings: The tank as designed and operated, and the containment <br /> area in which it is located are adequately anchored and are seismically sound. <br /> Initials: <br /> Leak Test: 191(g)(9)/192(k)(10) <br /> The waste oil storage tank and ancillary equipment were sealed and <br /> subjected to a slight positive pressure. A bubble test was performed on all <br /> tank seams and connections with no indication of leakage and good <br /> pressure retention. The secondary containment space was completely <br /> empty. <br /> Integrity testing findings: Based on the above noted integrity test and the results <br /> obtained from that test, the tank has sufficient integrity for its intended use. Initials: <br /> Tank Drawing: 19 1(g)(2)(E)/l 92(k)(2)(E)) <br /> Tank and fittings: See Attachment "B" <br /> Tank Dimensions (primary storage): <br /> 3.75' wide x 3.75' deep x 4.92' tall <br /> Tank Height: <br /> Overall: 5.29' <br /> Tank Gross Capacity (Volume): 500 gallons <br /> Lodi Honda 5 Title 22 Waste Oil Assessment <br />