Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> C C u N T AMENDED <br /> 8/17/2022 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MANTECA GAS& FOOD* 1229 E LOUISE AVE, MANTECA August 16, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION:Water was found in the 91 fill sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed approximately 4 ounces of liquid from the 91 fill sump and <br /> returned the sensor to its proper location. Immediately contact a properly licensed,trained, and certified contractor <br /> to address the water intrusion into the 91 fill sump under permit and inspection of the EHD. <br /> This is a repeat violation, Class II. <br /> 319 CCR 2635, 2637.2,2665, 2712 Failure to comply with overfill prevention equipment requirements. <br /> OBSERVATION: Overfill prevention testing was previously conducted late in August, 2019 and was due again by <br /> October, 2021.Testing was not conducted on time. <br /> REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October <br /> 13, 2018, and every 36 months thereafter, and within 30 days of completion of a repair. <br /> CORRECTIVE ACTION: Overfill prevention equipment was replaced on 8/15/2022 and testing was completed at <br /> that time. Ensure all future testing is conducted within required time frames. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended <br /> and replaces the initial report. Violations 116 and 203 were added and more information was added to violation <br /> 319. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the amended inspection report. <br /> FA0018327 PR0527041 SCO01 08/16/2022 <br /> EHD 23-01 Rev.9/16/2020 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />