ELECTRICAL SPECIFICATIONSGENERAL NOTES: 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA CODE OF REGULATIONS, INCLUDING THE FOLLOWING: TITLE 24, CCR, PART 2, 2019 CBC TITLE 24, CCR, PART 3, 2019 CEC TITLE 24, CCR, PART 4, 2019 CMC TITLE 24, CCR, PART 9, 2019 CFC ALL APPLICABLE LOCAL CODES. 2. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ETC. REQUIRED TO CARRY ON AND COMPLETE THE WORK. PERMIT BY OWNER. 3. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. 4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. 5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE NOTED OR REQUIRED BY CODE. 7. ALL LUMINAIRES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA ENERGY COMMISSION. 8. FLASH AND COUNTER FLASH ALL ITEMS PASSING THROUGH THE ROOF. ANY ROOF PENETRATIONS WILL BE APPROVED BY THE OWNER. ROOFING MFG. HAS SPECS. AS TO NOT VOID 20 YEAR WARRANTY. 9. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED AT LEAST 24" BELOW GRADE. BACKFILL IN 6" THICK, PROPERLY MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS, WALLS, EXISTING UNDERGROUND INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. 10. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND SWITCHES BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. 11. ALL EXIT SIGNS TO BE UNSWITCHED. NAMEPLATES & IDENTIFICATION: INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT, OR WITH A PLASTIC RESIN ADHESIVE GLUE, GOODYEAR "PLIEBOND" OR EQUAL. HVAC UNIT DISCONNECTS: 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. VERIFY AND CONFIRM THE ACTUAL MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT. 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE SIZE ON THE UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE FUSES OF THIS RATING. 3. FURNISH AND INSTALL ALL LINE VOLTAGE AND LOW VOLTAGE CONDUITS AND LINE VOLTAGE WIRING (LOW VOLTAGE WIRING BY OTHERS) TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL PLANS, UNLESS OTHERWISE NOTED. WIRING METHODS: 1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS, CONCEALED IN WALL AND CEILING U.O.N. 2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS ARE A. GALVANIZED RIGID STEEL. B. GALVANIZED STEEL EMT. C. LIQUID TIGHT STEEL FLEX -FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. D. FLEXIBLE STEEL CONDUIT -FOR INDOOR FINAL CONNECTIONS TO MECHANICAL EQUIPMENT (NOT TO EXCEED 36"). E. PVC CONDUIT SCHEDULE 40, UNDERGROUND. 3. NMC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. 4. MC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. WIRING DEVICES: UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT: A. WIRING DEVICES LEVITON # HUBBELL # P & S # SINGLE POLE SWITCH 1221 1221 20AC1 THREE WAY SWITCH 1223 1223 20AC3 DUPLEX CONV. OUT. 15A 5262 5262 5262 DUPLEX GFI CONV. OUT. GF5262 DEVICE PLATES: 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED EQUAL UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL BE RAISED METAL. 2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. WEATHERPROOF COVERS TO BE SNAP TYPE COVERS. 3. DEVICE PLATES FOR TELEPHONE AND COMPUTER OUTLETS TO BE PROVIDED BY OWNER'S VENDOR. ALL TELEPHONE AND COMPUTER SYSTEM WIRING BY OWNER'S VENDOR.SUPPORTS: 1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT. 2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS AND MACHINE SCREWS OR BOLTS. GROUNDING: 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC. PANELBOARDS: UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE, WITH THE NUMBER AND SIZE OF BREAKERS INDICATED ON THE PANEL SCHEDULE. SINGLE POLE, TWO POLE AND THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. THE PANEL DOORS SHALL HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICED BY EACH BREAKER. ALL BUSSING SHALL BE COPPER.WORKING CLEARANCES FOR PANELS & SWITCHBOARDS 1. COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C. SECTIONS 110-16 AND 384-4. TESTING: 1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS AND IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHETHER SUCH TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED, REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE. 2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE INSTALLATION IS COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE CONTRACT HAS BEEN PROPERLY AND FULLY EXECUTED. PROVIDE ALL INSTRUMENTS TO MAKE SUCH TESTS. LIGHT SWITCH, +48" TO TOP OF BOX• D = DIMMER• 3 = SWAY• P = PILOT SWITCH• os = LINE VOLTAGE OCCUPANCY SENSOR• T = TIMMER• VS = VACANCY SENSORWALL MOUNT OCCUPANCY SENSOR (LINE VOLTAGE)EMERGENCY LIGHTINGEXIT SIGN WITH 90 MIN BATTERY BACKUPWALL MOUNT EMERGENCY LIGHT WITH 90 MIN BATTERY BACKEXTERIOR LANDING EMERGENCY LIGHT. CONNECTTO INTERIOR EXIT SIGN FOR POWER.FIXTURES WITH INTEGRAL EMERGENCY BALLASTLIGHTING FIXTURES LINEAR FIXTURE• SQUARE = RECESSED• CIRCLE =SURFACEDOWNLIGHT, SQUARE = RECESSEDWALL MOUNT CEILING EXHAUST FANPOLE MOUNT AREA LIGHTELECTRICAL LEGENDMOUNTING HEIGHTSCONVIENCE OUTLETS, PHONE & DATA OUTLETS, +15" TO BOTTOMOF BOXSYSTEMS FURNITURECONNECTIONS +15" TOBOTTOM OF BOXESLIGHT SWITCHESFIRE ALARM MANUAL PULL STATION SHALL NOTREQUIRE "TIGHT GRASPING,PINCHING OR TWISTING OF THE WRIST"12" TYPICALTHERMOSTATOR WALL PHONEFINISHED FLOOR48" TO TOPOF BOXFINISHED CEILINGAUDIBLE FIRE ALARM APPLIANCENOT LESS THEN 90" AFF OR ATLEAST 6" BELOW CEILINGVISUAL APPLIANCE TO BE NOT LESS THAN 80" AFF MIN,AND NOT MORE THAN 96" AFF TO BOTTOMTITLE 24 LIGHTING CONTROLSLIGHT SWITCHCOMPONENTS OF DIMMING ROOM CONTROLLER• US = LOW VOLTAGE OCCUPANCY SENSOR (CAT 5 OR AS REQUIRED)• DRC = DIMMING ROOM CONTROLLER• PE = LOW VOLTAGE DIMMING PHOTOCELL (CAT 5 OR AS REQUIRED)• D = LOW VOLTAGE DIMMER (CAT 5 OR AS REQUIRED)• R = PLUG LOAD CONTROLLER• ADR = AUTOMATIC DEMAND RESPOSNE (FOR BUILDINGS OVER 10,000 SF)BASIC LIGHTING CONTROLSNOTES:1. FOR SUBMITTAL INCLUDE FACTORY CONTROL DRAWINGS.2. CONDUCT A CONTROLS PRE-CONSTRUCTION MEETING WITH CONTROLSSTARTUP TEAM. PROVIDE AGENDA AND ATTENDEES AS A SUBMITTAL. INCLUDEDEVICE I.D. TAGS, PROGRAMMING, CABLE ROUTING, PROGRAM AND TIMESCHEDULES AND DATE OF PROGRAMMING AND TESTING.3. CONTRACTOR TO HAVE SYSTEM FACTORY SUPPORT FOR START UP,PROGRAMMING AND COMMISSIONING. VERIFY OPERATIONAL HOURS WITH OWNERPRIOR TO COMMISSIONING.DRAFTING NOTATIONSKEY NOTE, SEE SCHEDULEEQUIPMENT TAG, SEE SCHEDULEREFERENCE TO A DETAIL VIEW "A" ON SHEET E-2NEW ELECTRICALEXISTING ELECTRICAL OR DEMOLISHED WHERE NOTEDEXISTING DEVICE, TO REMAIN IN OPERATIONREMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATIONREMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUITELECTRICAL LEGENDN##N##AE-2FIXTURE NOTATIONS:A,(b),C-12 FIXTURE TYPE "A", SWITCH "b", CIRCUIT C-12 ONE LINE DIAGRAMBUS / SWITCHBOARDPANELGROUNDMETERCURRENT TRANSFORMERPOTENTIAL TRANSFORMERDRY TYPE TRANSFORMERMOTORRELAY CR# = CONTROL RELAY TDR = TIME DELAY RELAY M = MOTOR STARTER CONTACTOR RELAY ETM = ELAPSE TIME METERCONTACT (OPEN)CONTACT (CLOSED)VARIABLE FREQ. DRIVEMOTOR OVERLOAD HEATERINDICATOR LIGHT (R) RED, (W) WHITEANTENNACIRCUIT BREAKER 50 AMP RATED, 3 POLEGFI = GROUND FAULT INTERRUPTER AFCI = ARC FAULT CIRCUIT INTERRUPTERDISCONNECT, RATED TO POWER SOURCEVOLTAGE AND AMPERAGE RATING FOR FUSEOR AS NOTEDFUSE, SIZE = 60 AMPSAUTOMATIC TRANSFER SWITCHENGINE DRIVEN GENERATOR RATING AS NOTED AGAINST THE UNIT.DRAW OUT DEVICEANSI RELAY50/360(e) (E)(r) (R)(RR)MCR150/3GVFDR521X1Y1Z1ATSP#16 ADDRESSIBLE INPUT CIRCUIT2#14 HARD WIRED NON-ADDRESSIBLE CIRCUITS2#12 VISUAL CIRCUIT2#14/SHIELDED AUDIBLE CIRCUITFIRE ALARM CONTROL PANEL (FACP)SMOKE DETECTORHEAT DETECTORHEAT DETECTOR IN ATTIC (194DEGREE)STROBECOMBINATION SPEAKER/STROBEEXTERIOR HORNPULL STATIONAHDHDSDFIRE ALARMFIRE ALARM ABBREVIATIONS:CD = CANDELLADSD = DUCT SMOKE DETECTOREOL = END OF LINE RESISTORNAC = NOTIFICATION POWER SUPPLYPIV = POST INDICATOR VALVETS = TAMPER SWITCHWF = WATER FLOW SWITCHWP = WEATHERPROOFMARKINGS:a### = CIRCUIT "a" DEVICE ###15CD = 15 CANDELLA VISUAL DEVICE1/2W = 1/2 WATT AUDIBLE DEVICETELEPHONE BACKBOARD, PROVIDE #8 GND TO SERVICE GROUNDCOMMUNICATIONS OUTLET, PHONE & DATAPHONE ONLY OUTLET, PREWIRED WITH CAT 5e CABLEDATA ONLY OUTLET JACK, PREWIRED WITH CAT 6 CABLEELECTRICAL POWERCOMMUNICATIONSALL LINE VOLTAGE WIRING IN CONDUIT, SEE GENERAL NOTES TICKS = # OF #12 WIRE, SHORT = HOT, LONG = NEUTRAL, DOT = GROUND, UNLESS NOTED OTHERWISE120V OUTLET, +18" TO BOTTOM OF BOX• S = SIGN• F = FLOOR• GFI = GROUND FAULT INTERUPTERCOUNTER OUTLETQUADRUPLEX OUTLETHALF SWITCHED OUTLETSOUTLETS ON EMERGENCY SYSTEMSDUCT SMOKE DETECTORJUCTION BOXMOTOR / DISCONNECTPANELBOARD TRANSFORMER / SWITCHBOARD AS NOTEDSDXX120v0-10V DIMMINGLIGHT FIXTURES120VOUTLETCONTROLLERWALL MOUNTSWITCH WITHON/OFF POWERAND RAISELOWER CONTROLDIMMING ROOM CONTROLLERWITH CAT5 INPUTS FOR LIGHT SWITCHES,MOTION SENSORS,DAY LIGHT PHOTOCELLCEILING OCCUPANCY SENSORCEILING PHOTOELECTRIC SENSORLINE VOLTAGEINPUTLINE VOLTAGECONTROL &0-10V DIMMERCONTROLTO SECONDSWITCHTO SECONDSENSOR277BRIDGECONTROLLERWHITE NORMALPOWER OUTLETIVORY SWITCHEDPOWER OUTLETSIGNCOLORED OUTLETS CONTROLLEDBY OCCUPANCY SENSORFALIOFCSeptember 2019SS T A TEERIILCWCENH OC28388AIRNL EWOITARCHEDAILLIMECT Checked By:Drawn By:Project No.:LDA Partners, Inc.Designers & Architects222 Central CourtStockton, CA 95204209.943.0405www.ldapartners.comClient:Architect:Project:450 COMMERCE COURTMANTECA, CA 95336HHHHTTTTIIIIMMMMSSSSC.C.C.C.DDDDRRRRAAAAHHHHCCCCIIIIRRRRNo. E14303No. E14303No. E14303No. E14303Exp. 6Exp. 6Exp. 6Exp. 6----30303030----21212121EEEELLLLEEEECCCCTTTTRRRRIIIICCCCAAAALLLLRRRREEEEGGGGIIIISSSSTTTTEEEERRRREEEEDDDDPPPPRRRROOOOFFFFEEEESSSSSSSSIIIIOOOONNNNAAAALLLLEEEENNNNGGGGIIIINNNNEEEEEEEERRRREEEEOOOOFFFFCCCCAAAALLLLIIIIFFFFOOOORRRRNNNNIIIIAAAASSSSTTTTAAAATTTTHCSEngineering50 years4512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 952194512 Feather River Dr #F, Stockton, CA 95219209209209209----478478478478----8270 | www.hcs8270 | www.hcs8270 | www.hcs8270 | www.hcs----eng.comeng.comeng.comeng.cominc.Enterprise Electric1250 S Wilson Way, Stockton, CA 95205 1250 S Wilson Way, Stockton, CA 95205 1250 S Wilson Way, Stockton, CA 95205 1250 S Wilson Way, Stockton, CA 95205 voice 209voice 209voice 209voice 209----464464464464----6627662766276627http://enterpriseelectric.yolasite.com/http://enterpriseelectric.yolasite.com/http://enterpriseelectric.yolasite.com/http://enterpriseelectric.yolasite.com/path://john/17/4BIM 360://Machado Sports/Machado Sports Electrical v21.rvtGENERAL NOTESE0.1AuthorChecker727-01-18PLAN CHECK5.28.21MACHADO SPORTS COMPLEX1020 MARSH CREEKEBMA INVESTMENTS###.###.####MANTECA, CA 95336SCALE: NTSLIGHTING CONTROLS DETAIL1SCALE: NTSSWITCHED OUTLET DETAIL2FIXTURE SCHEDULEType Mark LampDescriptionManufacturer Model Apparent LoadA LED LED HIGH BAY LIGHTING FIXTURE, 0-10V DIMMING DRIVERILP LIGHTING RB3-31L-U-40 224 VAAE LED SIMILAR TO "A" WITH EMERGENCY BALLAST224 VAB LED 2'x4' 4800 LUMEN LED CENTER BASKET TROFFER WITH 0-10V DIMMING DRIVER, UNIVERSAL VOLTAGE METALUX 24CZ 50 UNVL840 CD1 U49 VABE LED SIMILAR TO "B" WITH EMERGENCY BALLAST49 VAC LED 8' LINEAR SUSPENDED PENDANT, 0-10V DIMMING, BOTTOM AT +12'.CORELITE QZ-J2-WL-40L840-1D-UNV-STD-AC120-ST-866 VACE LED SIMILAR TO "C" WITH EMERGENCY BALLAST39 VAD LED 4' LED 4000 LUMEN LED WRAP SURFACE MOUNT FIXTURE, 0-10 V DIMMING DRIVER, UNIVERSAL VOLTAGE METALUX 4WSNLED-LD4-40SL-F-UNV-L840-CD1-U39 VADE LED 4' LED 4000 LUMEN LED WRAP SURFACE MOUNT FIXTURE, 0-10 V DIMMING DRIVER, UNIVERSAL VOLTAGE39 VAEXIT LED COMBINATION EXIT SIGN/EGRESS LIGHT UNIT, 90 MINUTE BATTERY BACKUP, UNIVERSAL MOUNT LITHONIA LHQMSW1R120/277ELN1 VAF LED SURFACE LED DOWNLIGHT, POLYCARBONBATE LENS, 0-10V DIMMINGHALO SMD6 16 VAFE LED SIMIALR TO "F" WITH EMERGNECY BALLAST OR MICRO INVERTER16 VAX2 LED EXTERIOR WALL MOUNT EMERGENCY EGRESS LIGHT FIXTURES WTH INGRAL BATTERY BACKUP FOR 90 MINIUTES,CONNECTED TO INTERIOR EXIT SIGN CIRCUITLITHONIA AFF 1 VANo. Description Date By5/18/2021, 8:35:15 AM21-0396Roseville Submittals6/8/2021, 1:58:25 PM21-0396LUMEN ARCEO
|