RFFORDR-TEST 209 744 0112 P. 03 <br /> INVOICE #JB000564 TEST DATE: 08/22/0-, <br /> Ak'FORDA-TE$T <br /> POB 36 - 26515 N SACRAMENTO BL <br /> THORNTON, CA 95686-0036 <br /> (209)794-0102 FAX (209)794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> FILLNER CONSTRUCTION, INC. LOVES TRUCK PLAZA <br /> 3633 SEAPORT AVE. 1510 JACKTONE RD. <br /> @ HWY 99 <br /> WEST SACRAMENTO, CA. RIPON, CA. <br /> 95691 <br /> CONTACT: BELL, CRAIG CONTACT: <br /> PHONE #: (916)372-1985 PHONE #: (209)5990740 <br /> ***** COMMENT LINES ***** <br /> TWO 20X DWST TANKS - BOTH DIESEL 2 WITH TESTTIMES 150 & 135 <br /> MINS. RESPECTIVLEY - PRESSURE SYSTEM - SYPHONED & MANIFOLDED <br /> GILBARCO EMC ATG <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND FUEL TANKS, THE <br /> THE MAXIMUM ALLOWABLE HOURLY LEAK/GAIN RATE IS .05 GALLONS. <br /> ULLAGE TESTS ARE ON A PASS/FAIL BASIS ONLY. <br /> TANK #l: DIESEL FUEL 2 TYPE: STEEL RATE: .030760 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: .05 <br /> TANK IS TIGHT. <br /> TANK #2: DIESEL FUEL 2 TYPE: STEEL RATE: .016315 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -.03 <br /> TANK ZS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1143 1 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: ��<< <br /> ZANE NIMMO, OTTO BRUNNMEIER ASSISTANTS <br />