Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-PS-87 2-PS-Diesel 3-PS-91 <br /> Sump Manufacturer Western FG Western FG Western FG <br /> Sump Depth (inches) 41" 44" 43" <br /> Sump Bottom to Top of 14" 15" 13" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:47 8:52 9:37 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 9:17 9:22 10:07 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Total Cont. Total Cont. Total Cont. Total Cont. <br /> Sump Depth (inches) 27" 27" 28" 27" <br /> Sump Bottom to Top of 13 1/2" 13" 13 1/2" 13 1/2" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:57 9:02 9:42 9:47 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:27 9:32 10:12 10:17 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />