120/208 VOLT COLOR CHART STANDARD EM01 <br /> DISPENSER CONTROL WIRNG 0 0 <br /> NOTE FUEL SHUTDOWN <br /> BRANCH CIRCUIT WIRING DONE BY SQUARE D IPaCS J 00 <br /> WILL BE COLOR CODED! <br /> A PHASE — BLACK WIRE @ SPECIAL FEATURES FOR FUELING CONTROLS: W Q <br /> B PHASE — RED WIRE <br /> C PHASE - BLUE WIRE 1 - TURBINE DISABLE SWITCH Q <br /> UGHTNIG CW R G ALL FACTORY BRANCH CIRCUIT WIRING ON SINGLE PHASE SWITCH A SPST SWITCH LOCATED ON EXTERIOR CABINET DOOR IS PROVIDED TO ALLOW PUMP AUTHORIZATION SIGNAL <br /> FROM DMEX MODULE TO BE "OPENED" AND PREVENT TURBINE OPERATION. RELEY "R3" (4P/DT) OPENS THE X J <br /> PANELS ARE TO BE WIRED IN BLACK. SIGNALS. WITH SWITCH IN OFF POSITION THE "HOOK" SIGNAL IS PREVENTED FROM REACHING TERMINALS 1A,2A,3A ' 1 <br /> ALL WIRING ABOVE #10 AWG TO BE PHASE COLORED ON 0 0 & 4A WHICH PREVENTS "VFC'S" FROM STARTING TURBINES. WITH SWITCH IN ON POSITION TURBINES OPERATE > m W V <br /> EACH END. NORMALLY. TYPICALLY USED TO DISABLE TURBINES WHEN FACILITY IS CLOSED. <br /> GENERAL NOTES FOR LIGHTING CONTROLS: m Z U_ <br /> REMOTE EMERGENCY SHUTDOWN BUTTON w J (3) <br /> 1 - OVERCURRENT PROTECTION FOR EACH LIGHTING CIRCUIT IS PRE-INSTALLED BY FIELD INSTALLED BY CONTRACTOR AT ?rW <br /> THE MANUFACTURE OF THE POWERBOX. NOTE: REMOTE PLANTER AREA JUMPER AT <br /> SQUARED IPaCS FOR TESTING Q Z / 1 z <br /> * BEFORE WIRING BRANCH CIRCUITS REFER TO PANELBOARD J <br /> REMOTE EMERGENCY SHUTDOWN BUTTON z <br /> 2 — CONTROL FUSE "L1" FOR LIGHTING CONTROL POWER MUST BE "5 AMPS". REPLACE SCHEDULES TO DETERMINE THE PHASE COLORS TO BE USED. FIELD INSTALLED BY CONTRACTOR AT o <br /> WITH THE SAME TYPE RATING AND FUSE. * ALL MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION OUTSIDE OF CONTROLLER ENCLOSURE w o a U (j)SHALL BE PROVIDED BY OTHERS. JUMPER AT SQUARE D IPaCS FOR TO PANEL DP BREAKER r") N c Q Q <br /> 3 — OUTDOOR LIGHTING SHALL BE CONTROLLED BY PHOTOCELL. TO BREAKER #2 ON QON2L4O TESTING — • — — — — — — — — — — — S — , FOR POWER TO PUMP #1 0 0 0 <br /> BREAKER MOUNTING BASE i i (#10 AWG) a_ a_ � — 0 <br /> E—STOP E—STOP � o <br /> LIGHTING CONTROL EQUIPMENT SHEET TO PHOTOCELL CONTACT TO TERMINAL "U14N" L - - - - - - - - - - - - - - - 1 I CD CD CD L U <br /> TO PANEL "A" GROUND BAR 1s i i 2 3 a w CN <br /> T#I <br /> EQUIPMENT VOLTS CONTACTOR PANEL OUT „ „ - F - (n <br /> TO PANEL A NEUTRAL BAR I I i I R CPN o 0 o Q O <br /> NUMBER AMPS CIRCUITS PUT ; ' RELAY BASE 30A RATING <br /> 1 SPARE 120 N/A <br /> FACTORY INSTALLED JUMPERS MUST BE PLACED IN I I 70OHN121 o U <br /> I I POSITION SHOWN FOR F.E. PETRO "IST-VFC"/ RED i I m m m m <br /> 2 120 L1 30 A-3 SW-1 10 I I JACKET "CPT" SYSTEMS - DO NOT REMOVE JUMPERS I I RELAY CUBE I I I _ _ _ m <br /> 3 120 A-5 I i 700HK36A1 ; i i 1 <br /> 4 SPARE 120 N A , I 1 I , I L_ � o � o <br /> CV CV <br /> P UMP I RELAY R3 CONTACTS SHOWN - o Qj <br /> 5 SPARE 120 N A I ' I REFER TO SHEET E-8 FOR I I BELOW 1A, 2A, 3A, 4A TERMINALS I _ _L_-_-_- — TO VFC PUMP # a o o �.., <br /> 6 SPARE 120 N A 1 i i PLLD WIRING DIAGRAM I I L - P <br /> 1 2 3 4 g 01NR34 SEE SHEET E8 00 r- o H <br /> 7 SPARE 120 L2 30 N A SW-1 i i I i �_ - _ - _ - _ - J CP P1 P2 P3 P4 Z <br /> 8 SPARE 120 N A A A A A <br /> I (>>> c») c») (») (») TO PANEL DP BREAKER <br /> 9 SIGNS SECURITY LIGHTS 1 120 A-15 PL I I I I I Q 4 4 4 4 4 RELAY CUBE <br /> I I I , 2 8501RS44P14V20 FOR POWER TO PUMP #1 <br /> 10 SIGNS SECURITY LIGHTS 2 120 L3 30 A-17 SW_2 I ' I I ,2> ,2> ,2> ,2> (#10 AWG) TO PANEL "DP" BREAKER <br /> 11 TANK PAD AREA LIGHT 120 A-13 I I I I I 2 2 2 2 2 <br /> 12 SPARE 120 N A I I I 14 FOR POWER TO PUMP #2a <br /> PUMP ( > c14> c14> c14� (14) s 6766 5 <br /> 2 ® ® ® O O O O O 0 ® 3 3 3 3 3 �4 �3 �2 �, ® 7 8 9 (#10 AWG) <br /> SWITCHES ARE � � � � 6®`®S 1 2 4 5 6 7 � � 4 3 2 1 S2 CPN 4 5 B <br /> MOUNTED ON DOOR. <br /> PL <br /> ® o� 9 9 r z c c c c TO) Q O Q O Q O Q O Q O 8 7 6 5 TT A AIN S3 CPN <br /> L1N L1S L1 CP N o BREAKOUT D ❑ 0000000o0000a N2 N0 m m m °° m 12 11 10 9 <br /> 1 1 1 1 1 1 N N P A B A B A B A B M M M M M w� w� w� w� w� I I I <br /> MODULE 2 3 4 30A RATING <br /> PUMP ® ® 0 ® AMPAMPAMPAMPAMPAMP ® ® ® ® ® 14 13 I I I <br /> O O � � � � � I I I <br /> 3 ATMR5 ATMR5 0 0 0 0 0 0 8501NR34 1 i L — I I I <br /> CANOPY LIGHTS SIGNS/FASCIA FUSE FUSE 5(+ 5(+ 5(+ 5(+ 5(+ R3 L _ _ _ _ _- - -TO 'VFC PUMP #1b i i LW—W <br /> OFF ON OFF ON PLP12 P11 P1C 99 1 TO 'VFC PUMP #2a <br /> TO PANEL "DP" BREAKER SEE SHEET E-8FOR _ <br /> 4 5 6 7 (#10 AWG)R TO PUMP #3a TO PANEL "DP" BREAKER W <br /> PUMP 8R3 7R3 6R3 5R3 FOR POWER TO PUMP #2b J N <br /> 12 11 10 s 7 8 s 10 AWG QWO <br /> (# ) <br /> CONNECT � >_ � <br /> RIBBON CABLE S5-EX CPN W O <br /> PL TO MODULE #19s 30A RATING s s <br /> (TOP RIGHT S4 CPN <br /> j 0 <br /> C, NETWORK BUS) % OFF ON j <br /> RESET SWITCH a I I I 30A RATING S <br /> NOTIFICATION i i i = <br /> w � Q <br /> Q I - - TO "VFC" PUMP #3a i i i O J <br /> L - - - - - - o <br /> REFER TO EQUIPMENT SHEET PL m ; ; 0) <br /> SEE SHEET E8 <br /> o TO PANEL DP BREAKER L _ _ _ _ _ _ TO 'VFC PUMP #2b <br /> *ORNELSIDE ONSAPR�R WIREID A � TURBINE DISABLE �� �° I � - - - � '� O � � <br /> SQUARE D TO CIRCUIT BREAKERS. FOR POWER TO PUMP #3b V 0) <br /> (#10 AWG) <br /> 7Q E STOP � 8 9 TO PANEL "DP" BREAKER <br /> 2 3 4 5 s 7 8 s ,o „ 12 FOR POWER TO PUMP #5a <br /> (#10 AWG) <br /> S6 CPN <br /> L1 L2 L3 <br /> 30A RATING 7 8 s <br /> 30A 30A 30A RESET o <br /> SEE NOTE 11 <br /> I I s7 CPN � <br /> LOCATED ON i I I 30A RATING <br /> CABINET DOOR I I h <br /> � - - -__ TO "VFC" PUMP #3b I I I <br /> I I I <br /> I I I A <br /> TO PANEL "DP" BREAKER I ` - - TO "VFC" PUMP #5a <br /> (#10 AWG) PUMP #4 L - - - - - � <br /> FIELD WIRING TO CP3 7 8 9 TO PANEL "DP" BREAKER <br /> FROM 70 <br /> TERMINAL <br /> DISCRETICONTRACTOR FOR POWER TO PUMP #5b <br /> TERMINAL STRIP Est FIELD WIRING (#10 AWG) <br /> TO CPN <br /> 30A RATING As-Built <br /> SHOWN ABOVE 7 8 s 09/01/2022 <br /> (BREAKOUT MODULE) <br /> FROMI I TO "STP-CBS" 1nHes cover crenuv,iNc 7:38:03 AM <br /> S8 CPN <br /> TERMINAL STRIP L - - -__- "PUMP #4" GAS ADDITIVE <br /> SHOWN ABOVE SEE SHEET E8 30A RATING �o QRpFESS/O,yq��� <br /> 2�' c� <br /> (BREAKOUT MODULE TO PANEL "DP" BREAKER I ' ' HAL P. GRUBB <br /> (#10 AWG) PUMP #6 <br /> PATENT 000 7 —' 67814 <br /> FIELD WIRING TO CP3 <br /> TO "VFC" PUMP #5b <br /> PENDING � NETWORK BUS TERMINAL AT CONTRACTOR e s L _ _ _ _ _ <br /> P <br /> DISCRETION FIELD WIRING <br /> g <br /> INPUT BREAKER ES3 -9T C / V 1 \- <br /> 120VAC MAX TO BREAKER 8c NEUTRAL BAR 30A RATING TO CPN F of CAL_ 0 <br /> - - - - - - ® _ _ ® TO PANEL "A" BREAKER 05127122 <br /> ® FOR DISPENSER #1 POWER FOR POWER TO ADDITIVE � <br /> CONTROLLER (#12 AWG) <br /> ® TYPICAL ALL - U L o <br /> OP1 OP2 OP3 OP4 DIPPOENsER (20 AMP MAX - #12 AWG.) o o Q Q <br /> 12 13 TO DISPENSER A � � � � ON 7 8 9 �; 0 Z > Z X <br /> - - - - - - - O FIELD <br /> WIRING o <br /> N FIELD WIRING TO CP3 30A RATING TO > > 0 cV m <br /> - - - - - - - - S®E TERMINAL AT CONTRACTOR CPN O o O N <br /> • ® SEE NOTE 1 6 DISCRETION 00 <br /> DM—EX NETWORK BUS I TO � iu <br /> MODULE I c Y CD> <br /> Au I ` - - TO ADDITIVE 3 CLo <br /> (D <br /> L - - - - - - CONTROLLER Q <br /> 0 <br /> RIBBON CABLE SUBMERSIBLE PUMP EQUIPMENT SHEET <br /> TO ADDITIONAL <br /> 9 DISPENSER MODULES RF EQUIPMENT VOLTS CONTACTOR PANEL OUT TO PANEL "A" BREAKER V <br /> FOR POWER (#10 AWG) O <br /> DM — EX MODULE FOR DISPENSER 1 # NUMBER AMPS CIRCUITS PUT — <br /> cn <br /> TYPICAL OF ALL GASOLINE DM—EX MODULES 1 DP-1 Q <br /> 2 FE PETRO IST #1a 208 1 30 DP-3 S1 7 8 9 U) <br /> DISPENSER DM — EX MODULE CHART 3 UNLEADED-1 DP-5 FIELD � o <br /> 4 DP-7 Esa WIRING t N <br /> DISP. BREAKER DESCRIPTION VOLTS AMPS PANEL 5 FE PETRO IST #1b 208 2 30 DP-9 S2 TO O CD <br /> N <br /> GENERAL NOTES FOR DISPENSER/PUMP CONTROLS: 6 UNLEADED-1 DP-11 30A RATING CPN •� V) & <br /> NUMBER CIRCUITS THE DISPENSER CONTROL WIRING SHOWN ON THIS DRAWING IS FOR ONE 7 D P-13 <br /> DM-EX 1 DISPENSER 1 FUELING POSITIONS 1 2 120 20 B-1 Q BEFORE STARTING THE ASSEMBLY PROCESS PLEASE DISPENSER. ALTHOUGH THE NUMBER OF DISPENSERS USED FOR EACH 8 FE PETRO IST #2a 208 3 30 DP-15 S3 I I I W <br /> DM-EX 2 DISPENSER 2• FUELING POSITIONS 3 4 120 2O B-2 READ ALL NOTES. JOB MAY VARY THE WIRING SHOWN IS TYPICAL OF ALL DISPENSERS. Q UNLEADED-2 DP-17 I I I � � N <br /> M E <br /> DM-EX 3 DISPENSER 3• FUELING POSITIONS 5/6 120 20 B-3 ALL FIELD WIRING TERMINALS MUST BE WIRED WITH A MINIMUM INSULATION THE PILOT LIGHTS SHOWN ON THIS DRAWING ARE TO VISUALLY VERIFY THE 10 DP-19 I I I Q� > O <br /> 10 OPERATION OF EACH PUMP. ALL PILOT LIGHTS SHOWN SHOULD BE 11 FE PETRO IST #2b 208 4 30 DP-21 S4 I I `� C Q 00 fV <br /> DM-EX 4 DISPENSER 4• FUELING POSITIONS 7 8 120 20 B-4 Q RATING I 60'T IF CIRCUIT IS RATED LESS THAN 100 AMPS. ORA MOUNTED ON THE DOOR OF THE DISPENSER PUMP CONTROLS SECTION. 12 UNLEADED-2 DP-23 � - - -L - - -TO PERMEATOR PANEL •- < N <br /> MINIMUM INSULATION RATING OF 75'C IF CIRCUIT IS RATED OVER 100 / +0 <br /> DM-EX 5 DISPENSER 5• FUELING POSITIONS 9/10 120 20 B-5 AMPS. ALL MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION SHALL BE THE MOMENTARY SWITCHES FOR "FUEL SHUTDOWN" AND "FUEL RESET" 13 DP-2 m Q <br /> DM-EX 6 DISPENSER 6• FUELING POSITIONS 11/12 120 20 B-6 PROVIDED BY OTHERS. �� SHOWN ON THIS DRAWING SHOULD BE MOUNTED ON THE DOOR OF THE 14 FE PETRO IST #3a 208 5 30 DP-4 S5 � N � 3 <br /> DM-EX 7 DISPENSER 7• FUELING POSITIONS 13/14 120 20 B-7 DISPENSER/PUMP CONTROLS SECTION. 15 UNLEADED-3 DP-6 Ln }; N <br /> DM-EX 8 DISPENSER 8• FUELING POSITIONS 15416 120 20 B-8 Q WHEN CONTROLLED LOAD IS A MOTOR, CIRCUITS MUST HAVE THERMAL (# ) i <br /> PROTECTION INTEGRAL TO MOTOR OR PROVIDED BY OTHERS. Q WIRING IS TYPICAL OF ALL DISPENSERS. GROUND CONDUCTOR 12 AWG 16 DP-8 m o N C Ln o <br /> DM-EX 9 DISPENSER 9• FUELING POSITIONS 17/18 120 20 B-9 12 MUST ALSO BE RUN FROM EACH DISPENSER TO THE GROUND BAR OF THE 17 FE PETRO IST #3b 208 6 30 DP-10 S6 m V 00 ) Lo <br /> CD <br /> DM-EX 10 DISPENSER 10• FUELING POSITIONS 19420 120 20 B-10 DISPENSER/PUMP CONTROL PANEL. 18 UNLEADED-3 DP-12 CD <br /> DM-EX 11 DISPENSER 11 FUELING POSITIONS 21 22 120 20 B-11 Q THIS DRAWING CONTAINS ALL THE FACTORY WIRING REQUIRED TO Q i <br /> ASSEMBLE THESE CONTROLS. FOR A COMPLETE EXAMPLE OF ,3 DISPENSER "AC" (POWER) AND "DC" (DATA) TYPICALLY RUN IN SAME 19 DP-14 0 <br /> CONDUITS, OR PER DISPENSER MANUFACTURERS REQUIREMENTS. 20 FE PETRO IST #5a 208 7 30 DP-16 S7 ° <br /> DM-EX 12 DISPENSER 12• FUELING POSITIONS 23/24 120 20 B-12 ALL FIELD WIRING TO THESE CONTROLS PLEASE SEE THE 8-1/2" 21 PREMIUM DP-18 <br /> X 11" DETAIL SHEETS INCLUDED IN THE INSTALLATION BOOK. ,a SEE DISPENSER INSTALLATION DIAGRAMS FOR TERMINATION LABELING. 22 DP-20 a <br /> QTHE WIRE GAUGE USED TO ASSEMBLE THESE CONTROLS VARIES 23 FE PETRO IST #5b 208 8 30 DP-22 S8 LLJ <br /> 5 THROUGHOUT. TO DETERMINE WIRE SIZE THAT SHOULD BE USED PLEASE ,5 ALL FIELD WIRING TERMINALS MUST BE WIRED WITH A MINIMUM INSULATION 24 PREMIUM DP-24 N <br /> CHECK THE AMPERAGE OF THE CIRCUIT CONTROLLING THESE RATING OF 60'C. 25 A-1 CD <br /> COMPONENTS. THE AMPERAGE CAN BE OBTAINED FROM THE FACTORY INSTALLED "REMOTE OFF" JUMPERS ON DM—EX MODULES MUST 26 ADDITIVE BATCH CONTROLLER 120 9 30 N A ES1 <br /> PANELBOARD SCHEDULES LOCATED IN THIS SET. ,s 27 ZL N A E <br /> REMAIN IN PLACE DURING NORMAL OPERATION. REMOVING THIS JUMPER AND •E <br /> IF THERE ARE ANY QUESTIONS ABOUT THE PLACEMENT OF ANY WIRING INTO A "PAN SENSOR" SYSTEM PROVIDES INDIVIDUAL SHUTDOWN OF 28 DP-26 <br /> s NON—STANDARD DEVICES ON THE DISPENSER/PUMP CONTROLS SCREEN EACH DISPENSER. 29 FE PETRO STP #4 208 11 30 DP-28 ES2 <br /> PLEASE CONTACT THE MANUFACTURER TO DETERMINE PROPER PLACEMENT. GAS ADDITIVE E <br /> THE WIRE SIZE AND NUMBER OF CONDUCTORS REQUIRED FOR 30 7 N ACD <br /> i <br /> WHEN VARIABLE SPEED CONTROLLERS ARE FIELD INSTALLED, THE �� COMMUNICATION/DATA (DC) WIRING MUST BE DETERMINED BY THE 31 DP-30 0 <br /> PLACEMENT OF THE EQUIPMENT SHALL BE DETERMINED BY THE SPECIFICATIONS OF THE DISPENSER MANUFACTURER. TYPICALLY 2 32 SPARE 208 12 30 DP-22 ES3 0 <br /> ('A__'� Square D ShopDrawingWiringELECTRICAL CONTRACTOR. CONDUCTORS (NORMALLY SHIELDED CABLE) ARE REQUIRED WHEN CARD33 <br /> READERS IN THE DISPENSER ARE USED. 34 7 DP-25 0 � �, o <br /> Q THE STANDARD LIGHTING/DISPENSER MANAGER MODEL IS WARNING: PROPER JUMPER PLACEMENT IS CRITICAL FOR THE CORRECT 35 ARID PERMEATOR 120 13 30 DP-27 ES4 z O N W <br /> SCALE: NTS EXPANDABLE TO 8 DISPENSERS. ,s OPERATION OF THE FUELING CONTROLS. REFER TO 8-1/2" X 11" DETAIL 36 7 DP-29 0 <br /> SHEETS IN BOOK FOR THE CORRECT APPLICATION T <br /> LL <br />