Interstitial Liquid Sensor Installation Guide Sensor Description <br /> 7. Using wire nuts, connect the two-wire sensor cable to the field wires in the sensor junction box (Figure 2). Seal <br /> wire nuts with epoxy sealant following the instructions in Figure 3. <br /> + Red <br /> To From <br /> TLS Seal-off <br /> Console — Black Sensor <br /> • <br /> \1/2" rigid <br /> conduit <br /> isstwir.eps Epoxy sealed connections in a <br /> weatherproof junction box <br /> Figure 2. Sensor Field Wiring Diagram <br /> A ( C From probe, <br /> sensor,or <br /> transducer To console <br /> Make sure that <br /> the ends of cable <br /> sheathing are sub- <br /> / merged in sealant Tie wrap <br /> 1 Wire nuts <br /> Instructions: <br /> NOTE: When temperature is below 50°F (10°C), keep 4. Mix thoroughly to a uniform color by squeezing <br /> resin in a warm place prior to mixing (e.g., in an contents back and forth 25-30 times. <br /> inside pocket next to body). 5. Squeeze mixed, warm resin into one end of bag and <br /> 1.Open epoxy sealant package,and remove resin pak. cutoff other end. <br /> 6. Slowly insert wiring connections into sealing pack <br /> 2. Holding resin pak as shown in A,bend pak along long until they fit snugly against the opposite end as <br /> length. shown in C. <br /> 3. As shown in B, firmly squeeze the RED SIDE of the 7.Twist open end of bag and use tie wrap to close it off <br /> resin, forcing it through the center seal and into and position the tie wrapped end up until the resin <br /> BLACK SIDE. jells. <br /> CAUTION:Epoxy sealant is irritating to eyes,respiratory system, <br /> O4) O and skin.Can cause allergic skin reaction.Contains:epoxy resin <br /> and Cycloaliphatic epoxycarboxylate. <br /> Precautions:Wear suitable protective clothing,gloves,eye,and <br /> face protection.Use only in well ventilated areas.Wash <br /> thoroughly before eating,drinking,or smoking. conso1es\epxy2w.eps <br /> Figure 3. Epoxy sealing example <br /> 6 <br />