Laserfiche WebLink
Well Chlorination Service Information: F.C.G. &RV Domestic Well #2 <br />Location. French Camp Golf Course & RV Park <br />3919 French Camp Road <br />Manteca, CA. 95363 <br />Well Site Location: In a parking area island, (covered by a small wood structure) <br />1808 North of French Camp Road <br />135ft West of the Entrance Drive <br />Known Well Data: 6" X 280ft. Steel Domestic Water Well <br />Standing Water Table: 41.2ft. @ 18in. above grade. <br />Total Well Capacity: 411.60ga1, <br />Standing Water Capacity: 351.03gal. <br />Known Pump Data; 114P, 230V, l Phase 11 /4in. Submersible Pump System <br />96ga1. Diaphragm Tank (South end of the Maintenance Building) <br />Distribution. System: Unverifiable at time of service. 11/4in. connected system <br />services the existing Office Restroom, Maintenance <br />Shop Restroom and Hose Bibs on each building. <br />Also a gated connection to Pro Shop Restrooms and <br />Kitchen. <br />Service: Super Chlorinated Well 5-24-01/1200.... 50ppm+ and re -circulated system. <br />Checked free Chlorine Residual 5-25-01/0730.... 0.00ppm <br />Super Chlorinated Well 5-25-01/0800.... 50ppm+ <br />Checked free chlorine residual 5-26-01/0730.... 0,00ppm <br />Ran well to drain. <br />Comments: Well may have water moving through well that may have effected <br />24hr residuals. <br />Zo 39dd dHVD HON3�1 0GLTT8VCZG0Z 5T:5T 6o0Z/oZ/Z0 <br />