CORRECTIVE ACTIONS AFTER SOURCE INYESTIGATIQN: <br /> Upon correcting the identified physical deficiencies,disinfect the water in the well casing using NSF 61 approved chlorine and AWVVA procedures, Apply <br /> chlorine at 60 ppm concentrations into the well. Circulate the chlorinated water within the well, up through the pump column,into the pressure tank and back Clown <br /> into the weal by turning on time well and opening a valvelhose bib at ttte pressure tank. Connect a hose to a hose bib at the pressure tank that terminates with a <br /> small diameter wand able to spray a circular spray pattern to wet the sides of the weft casing and pump column above the water table, when the wand is inserted <br /> into the wellhead seal access port. Circulate the chlorinated water down the sides of the well casing for 30 minutes, as noted above. Test the chlorine residual <br /> through this process to ensure 50 ppm chlorine residual. dose well as needed to maintain 50 ppm chlorine residual, After 30 minutes, tum off the well, close the <br /> valvefhose bib at the pressure tank, disconnect the hose, and seal the wellhead at access port to be water tight, A3iow 12-24 hours for the 50 ppm chlorinated <br /> water to reside in the well. A successful disinfection requires a residual of at least 10 ppm to be present after the 18-24 hours. If the chlorine residual is found to <br /> be non-detectable, then the disinfection process may not have been successful. Repeat the disinfection process. If residual is at least 10 ppm,flush the well <br /> water to waste and resample the well for Hort detect ehlorina residuals. Contact your lakoratofy to cdlegt a wellhead sampi to test for chlorine residuals and TO <br /> bacteria, using_enumeration test methods, Once SOURCE is absent proceed with disinfecting DISTRIBUTION SYSTEM as noted below. Contact the END if you <br /> need guidance with this procedure, <br /> If Well Confinisets to Fails. Investigate the well casing using a camera and record the findings to determine the condition of the casing, movement of <br /> groundwater in and out of the well column, presence of o]I from a turbine pump, tree roots, other contributing deficiancles that may cause the well to test positive <br /> for TC_ Submit a copy of the well down-hole investigation recording to the EHD and contact the EHD for guidance at(209)468-3420. <br /> INVESTIGATION of a TCR INCL. If the SOURCE is absent and the DISTRIBUTION SYSTEM is positive for TC:: Have your laboratory collect additional "Other" <br /> TC Bacteriologicaf samples to determine If the pressure tank, storage tank, andlor treatment system is a TC source. Collect a sample down stream of these <br /> components to determine if the bacteriologlcal problem begins at these components. If the initial"tither"result is absent for TC, then go to DISTRIBUTION <br /> SYSTEM & investigate the distribution lines clown stream of these components, ff the°'Other" result is posiffv�, then sample downstream of each component to <br /> further ID where the 5y tem begins to fail for TC. Perform an inspection as detailed below in the Treatrr►ent Storage, and Pressure Tank sections. <br /> 4g, <br /> , g.�r -r._ •,c ,ice,-'V >. _ 5 � .,�.. <br /> Inspect each point where disinfectant Is added and report, any leaks? YIN <br /> is ttie disinfectant feed tank full with chlorin & what is the ppm concentration? A' <br /> Are there contaminants in the chlorine feed tank?YIN 1 A _ <br /> What is the disinfectant residua] down stream of injection point? <br /> What is the disinfectant residual at the end points of the system or repeat sites? A drop in chlorine indcates the <br /> Repeat 1f Repeat 21 Repeat 3l' ,End pt 11 End locatlon of the problern, Find where <br /> pt.21 the initial decrease begins, clown <br /> stream of the injection point, <br /> is the disinfectant teed tank and equipment skwad Ina pmh5cted manner ti.e.Is tank Stored ouI of the House equipment in an enclosure to <br /> sun,p(otsaW From rain,lid ks sealed on tank&lid sealed at tins,no openings to lank,irrigation I exclude vermin and elements. <br /> water is not sprinklin over the eVOrtent,birdsfvermin are not nesting ovetiead)? YIN <br /> Is the tank's water fill line protected by a back flow device or proper air gap? YINInstall a proper back flow device on <br /> fresh water flit line. <br /> What is the MPN concentration of bacteria in each vessel'? i <br /> What is the media in each vessel? j <br /> Is a vessel not in use, is it valved ofd YIN <br /> Inspect each treatment vessel for leaks at joints,valves,connecbans at top and bottom of <br /> the vessels man-ways not closed. Note if a leak was found and where at each vessel. <br /> Was the med is recently exchanged in a vessel or repair made to a vessel? YIN This vgxk may have caused TCR MGL. <br />