Laserfiche WebLink
TAIT <br /> �IMI�TO tNmawme7 S CA <br /> SUMMARY TEST REPORT FOR USE WITH LEIGHTON O'BRIEN PM2 LINE TESTER <br /> CLIENT: AT&T UE042 DATE: 7/14/2022 <br /> LOCATION: 345 North San Joaquin St. Stockton California 95202 <br /> skeet CRY State <br /> REASON FOR TEST: AT&T Request.System Integrity Nat.Local CUPA on site Fred Ernest. <br /> SPECIAL INSTRUCTIONS: Above ground pressurized line.Leighton O'Brian Diagnostic Report Number LIS154175 <br /> I declare under penalty of perjury that I am a licensed tank tester In the State of <br /> California and that the Information contained In thIs report Is true and correct to the <br /> best of my knawlefte. <br /> TECHNICIAN: Pat Banbury 90.1413 <br /> Name Signature License Number <br /> MAKE AND TYPE OF PUMP OR DISPENSERS Transfer Pump <br /> COVER OVER LINES Above Ground APPROX. BURIAL DEPTH NA <br /> Product Name Line teat Wet Test Start Test End Test Cert No. Test Results <br /> or Dr Time Time Pressure !_ <br /> Diesel UE04200011 WET 8:40 AM 9:20 AM 55.38 PSI 189726 Pass <br /> UE042A00S 0.018 allhr. <br /> COMMENTS: Test conducted from UE042UD01 above ground transfer pump to UE042AODS roof top belly tank. <br /> Above ground double wall steel piping. <br /> Note:These results need to be submitted with the final Leighton O'Brien UPSS Test Report. <br />