Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑✓ Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum p Hydrostatic <br /> Test Equipment Used: INCON TS-STS <br /> Sump/UDC ID Fill Manway Piping <br /> Sump Manufacturer N/A N/A N/A <br /> Sump Depth (inches) 40" 36" 40" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 9-- a° 16" <br /> (inches) <br /> Test Start Time 9:20am 9:20am 9:20am <br /> Initial Reading 1.0936 in. 3.2307 in. 4.0915 in. <br /> Test End Time 9:35am 9:35am 9:35am <br /> Final Reading 1.0932 in. 3.2307 in. 4.0912 in. <br /> Change in Reading -0.0004 in. 0 -0.0003 in. <br /> Pass/Fail Criteria 0.002 in. 0.002 in. 0.002 in. <br /> Tightness Test Results p Pass ❑ Fail p Pass ❑ Fail ❑✓ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results D Pass ❑ Fail D Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />