ELECTRICAL SPECIFICATIONS
<br /> 0
<br /> A. GENERAL REQUIREMEN
<br /> lA
<br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA �.
<br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: CHRISTY N16 PULLBOX D' ,� 0
<br /> ` -- --��
<br /> TITLE 24, CCR, PART 2, 2007 CBCSEE ELECTRICAL SITET
<br /> TITLE 24, CCR, PART 3, 2007 CEC P83 PLAN FOR CONTINUATION ��..
<br /> TITLE 24, CCR, PART 4, 2007 CMC
<br /> TITLE 24, CCR, PART 9, 2007 CFC
<br /> ALL APPLICABLE LOCAL CODES SEE ONE LINE PB4
<br /> DIAGRAM
<br /> 2. ELECTRICAL CONTRACTOR SHALL VERIFY POWER, TELEPHONE AND CABLE TV ..--
<br /> SERVICES AT THE SITE PRIOR TO BIDDING. SERVICES TO CONFORM TO UTILITY COMPANY
<br /> REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL CONTACT THE UTILITY µ 0 "" 10
<br /> 0 ��
<br /> COMPANIES IN A TIMELY FASHION TO ARRANGE FOR SERVICE INSTALLATIONOF
<br /> ° __ �°` �`
<br /> _r.
<br /> PER UTILITY COMPANY REQUIREMENTS SO AS NOT TO DELAY THE INSTALLATION ���-- �" _m'm � �.�
<br /> OF SERVICES AND PAY ALL CUSTOMER CHARGED SERVICE COSTS. _ "D o3.
<br /> }�
<br /> CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ETC. REQUIRED
<br /> _W '-..
<br /> TO CARRY ON AND COMPLETE THE WORK. COUNTY TO PAY FOR PERMITS. —
<br /> 4. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT,
<br /> AREA OF WORK
<br /> TRANSPORTATION AND PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE "�-• ------
<br /> INCIDENTAL TO PROPER EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" NORTH !
<br /> WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED
<br /> HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT NORTH
<br /> ENLARGEDTHEREOF. PUMP ELECTRICAL PLAN 5. ALL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERSSCALE I/16"={'-0" KEY PLAN
<br /> LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR
<br /> THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL NTS
<br /> SERVICE IS REGULARLY FURNISHED BY THAT AGENCY.
<br /> 6. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH X \ f
<br /> THE SIZE AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER
<br /> POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT -�
<br /> DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL EXISTING DISTRIBUTION
<br /> BE RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID PANEL "A"
<br /> INTERFERENCE WITH OTHER TRADES. .
<br /> 8, __RACEWAYS & WIRING SYSTEMS
<br /> 1. ALL LINE VOLTAGE WIRING SHALL BE INSTALLED IN RACEWAYS. RACEWAYS
<br /> SHALL BE PVC TYPE DB-120 UNDERGROUND WITH PVC SCHEDULE 40 BENDS.
<br /> CONDUIT STUB-UPS THROUGH SLAB SHALL BE PVC SCH. 40. LIQUID TIGHT
<br /> FLEXIBLE CONDUIT FOR FINAL OUTDOOR CONNECTIONS.
<br /> 2. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THHN/ EXISTING CONDUITSTHWN, �---�
<br /> 600V, 90'/75' UNLESS OTHERWISE NOTED OR REQUIRED BY CODE. NEW CABLES SEE
<br /> ONE LINE DIAGRAM f
<br /> 3. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL f
<br /> BE INSTALLED AT LEAST 24" BELOW GRADE UNLESS OTHERWISE NOTED. BACKFILL EXISTING CONDUITS ,T
<br /> IN 6" THICK, PROPERLY MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED "
<br /> TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE NEW CABLES SEE
<br /> SURFACES, ROADWAYS, WALKS, CURBS, WALLS AND EXISTING UNDERGROUND ONE LINE DIAGRAM P LLBOX
<br /> INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER.
<br /> NAMEPLATES & IDENTIFICATION
<br /> 1. INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT,
<br /> ETC. NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4
<br /> PHILLIPS ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS.
<br /> D. SUEPORTS
<br /> 1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR zoo B D G
<br /> ALL ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT.
<br /> 2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS,
<br /> TO METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION f / EXISTING
<br /> ANCHORS AND MACHINE SCREWS OR BOLTS. /
<br /> / PULLBOX
<br /> E. GROUNDING
<br /> / P
<br /> 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND /
<br /> SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, TRANSFORMERS, MOTOR CASES, /
<br /> ETC.
<br /> SEE ONE LINE
<br /> -. RV PEDESTAL DIAGRAM
<br /> 1. PEDESTAL FOR SITE FOR LOT LIGHTS AND RECEPTACLES SHALL BE NEMA 3R,
<br /> FREE STANDING, AS MANUFACTURED BY MILLBANK, TYPE U5200-XL--75 OR APPROVED 4w /
<br /> EQUAL WITH DISTRIBUTION SECTION WITH BRANCH CIRCUIT BREAKERS AND INTEGRAL /
<br /> RECEPTACLES AS SHOWN ON THE PLANS. ETC. FINISH TO BE STANDARD. ALARM HORN WITH /
<br /> 2. SWITCHBOARD SHALL BE WEATHERPROOF, AS SPECIFIED ON THE SIGN NEXT TO
<br /> /
<br /> PLANS, FREE STANDING WITH LOCK PROVISIONS FOR LOCKING BY THE OWNER (e)PUMP PANEL LEACH /
<br /> 3. UNIT SHALL BE MANUFACTURED FOR DIRECT BURIALFIELD .. AGROUND PULLBOX SCHEDULE. ALARM /
<br /> 4. ALL BUSSING SHALL BE COPPER INCLUDING GROUND BUS. TAG PULL BOX TYPE
<br /> � ���' ^_ / PB1 CHRISTY N16
<br /> 5. DISTRIBUTION SECTION SHALL BE OF CIRCUIT BREAKER TYPE UTILIZING -...�._� '�--//
<br /> THERMAL MAGNETIC TYPE CIRCUIT BREAKERS WITH FRAME SIZES AS SHOWN ON P62 CHRISTY N16
<br /> / PB3 CHRISTY N16
<br /> SINGLE LINE DIAGRAM. �
<br /> 6. ALL CIRCUIT BREAKERS SHALL BE IDENTIFIED WITH BAKELITE ENGRAVED /%i/ �zd� �, •
<br /> PB4 CHRISTY N 16
<br /> NAMEPLATES. ca � � .- -� A�f'ACH!TO SIDE
<br /> 7. SPACES FOR FUTURE CIRCUIT BREAKERS SHALL INCLUDE ALL HARDWARE, BUS "` -- ( BRIDGE.
<br /> TAPS, ETC. NECESSARY TO PERMIT THE FIELD INSTALLATION OF BREAKER UNITS. '~
<br /> THE HARDWARE SHALL BE EQUIPPED WITH INSULATING TUBE OR BOOT. No,, s !H. PITS
<br /> SITE LIGHTING 3�0� C0 ROL CABLE`
<br /> .. FOR LEACH FIELD
<br /> 1. PROVIDE POLE MOUNT, POST TOP SITE LIGHTING, COMPLETE WITH INTEGRAL 'S .ALARM SEE ONE
<br /> PHOTOCELL CONTROLS AS SHOWN ON THE PLANS. LINE DIAGRAM.
<br /> 2. MINIMUM CONDUIT FOR SITE LIGHTING SHALL BE 3/4" WITH MINIMUM WIRE SIZE TO - - P132i � C _ ---"
<br /> BE #10, COPPER. P81 BEST F,0 - _
<br /> I. TESTING /
<br /> r! ��
<br /> 1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS
<br /> AND IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND 6 B _ # 5KVA TRANSFbRME
<br /> GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHETHER SUCH SEE ENLARGED PUMP i \ PAEL "P
<br /> THIS SHEET "
<br /> TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED, ELECTRICAL PLAN --
<br /> REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE. ROTATION OF ALL MOTORS f t J \ /
<br /> . - i j PUMP CONTRO
<br /> SHALL BE CHECKED AND CORRECTED, IF NECESSARY, AFTER FINAL CONNECTIONS ARE ( i \\ PANEL CPL1
<br /> /
<br /> MADE. 1
<br /> 2. DEMONSTRATE TO THE OWNER THAT THE ENTIRE INSTALLATION IS COMPLETE
<br /> ' It ,/ •_` - 'e SEE ONE
<br /> IN PROPER OPERATING CONDITION AND THAT THE CONTRACT HAS BEEN PROPERLY , / , LINE DIAGRAM \ _ �
<br /> AND FULLY EXECUTED. PROVIDE ALL INSTRUMENTS TO MAKE SUCH TESTS. / ,� s \ e
<br /> — / _.�..__.mol
<br /> J. PULLBOXES __.._. ...� Y ,/ .� � �, r-' .,�4--�--" �' \ �
<br /> 1. PROVIDE PULLBOXES WHERE SHOWN OR REQUIRED BY CODE. 1 I PB3d/ , i �" _ L
<br /> 2. SIZE PULLBOX PER CODE. `"� I "
<br /> •
<br /> 3. 0 () 0
<br /> 00
<br /> PROVIDE FULL VEHICULAR RATED TRAFFIC COVERPLATE WHERE PULLBOXES
<br /> ARE LOCATED IN AREAS WHICH COULD HAVE VEHICULAR TRAFFIC. - NORTH
<br /> \
<br /> - �. , HCS ENGINEERING, INC.
<br /> ELECTRICAL SITE PLAN_
<br /> E14W3 CONSULTING ELECTRICAL ENGINEERS
<br /> p. 6--30-09 4512 FEATHER RIVER DRIVE SUITE '°F"
<br /> SCALE I"=30-0" �'9r�FCTR►CP�� STOCKTON, CA 95219 (209)478-8270
<br /> tnpFCA1-�F� E—MAIL ADDRESS — BIIIOhcs--eng.com
<br /> CA:000-227-2600 REVISION S
<br /> PROJ.—_ 200$122--DES.. _ WDW—ENG.` IRKS -„
<br /> O NO. D E S C R I P T 1 0 N DATE I BY JOB NO. 07160 MICKE GROVE ZOO BACKWATER AND SEWAGE DISPOSAL SYSTEM SHEET
<br /> ° BENCH MARK: . Civil Engineering
<br /> CHISELED CROSS ON CONCRETE AT
<br /> �....—... .................mew.......................Res......................, . Land
<br /> Surveying DATE 05/23/08
<br /> WEST SIDE EXISTING AVIARY AS a Structural Engineering DESIGN WDW ELECTRICALESHOWN ON THIS PLAN. ELEVATION . Planning SITE PLAN
<br /> 37.06 ' DRAWN WDW
<br /> 4045 Coronado Avenue • Stockton, CA 95204
<br /> NV:800-227-2600 209 943-2021 • Fax: 209 942-0214 CHECKED RCS 11793 M I C K E GROVE ROAD OF 3 SHEETS
<br /> E N G I N E E R I N G . INC. E—Mail: mailOslegfriedeng.com DRAWING FILE NO.
<br /> F.B. NO. LODI , CALIFORNIA G
<br />
|