Laserfiche WebLink
Board Power W I., MR",3 ® Ji I I <br />If the green power ELECTRICAL SHOCK HAZARD <br />Aatus indicators are not 0:S=r4necl ail pc:,'e: wwces "Wcr <br />luminated: Etta;g. FaiuEeW•asac :, res=i <br />^'�Eil.1t3S E^jUR';1"c'!✓; r7. <br />1. Check to see if the <br />fuses on the circuit board are blown. <br />2. Check to see if the incoming controlialarrn power is present <br />at TBI -1 and TBI -Z <br />If voltage is present and fuse is not blown, please call factory for <br />assistance. <br />Circuit Breaker (optional) <br />Check each pole of the circuit breakerfor proper resistance reading <br />using the following procedure: <br />Warning: Disconnect all incoming power to control panel. <br />Failure to do so could result in serious or fatal electrical shock. <br />1. Isolate the circuit breaker by disconnecting either the line side <br />or load side wires. <br />2. Place the ohmmeter lead's across the corresponding line and <br />load terminals of each pole. <br />3. With the ohmmeter on the R X 1 scale and the breaker in <br />the OFF position, the reading should be infinity (very high <br />resistance). With the breaker in the ON position, the reading <br />should be nearly zero ohms (very low resistance). If the <br />readings are riot as stated, replace the circuit breaker with <br />one of the sante ratings. <br />Alarm Horn <br />Moving the test/normal/silence switch to the test position or <br />activating the alarm float should turn on the alanm horn. If the horn <br />does not sound, replace horn with same type. <br />Alarm Light <br />Moving the testtnormallsilence switch to the test position or <br />activating the alarm float should turn on the alarm light. If the light <br />does not activate, replace with bulb of same type. <br />SJE-RH4MSUS1" warrants to the original consumer that this prod- <br />uct shall be free of manufacturing defects for five years after the <br />date of consumer purchase. During that time period and subject <br />to the conditions set forth below, SJE-RHOMBUS-' will repair or <br />replace, for the original consumer, any component which proves <br />to be defective due to defective materials or workmanship of SJE- <br />RHC MBUS". <br />ELECTRICAL WIRING AND SERVICING OF THIS PRODUCT <br />MUST BE PERFORMED BY A LICENSED ELECTRICIAN. <br />THIS WARRANTY DOES NOT APPLY: (A) to damage due to <br />lightning or conditions beyond the control of SJE-RHOMBUS-; (B) <br />to defects or malfunctions resulting from failure to properly install, <br />operate or maintain the unit in accordance with printed instructions <br />provided; (C) to failures resulting from abuse, misuse, accident, or <br />negligence; (D) to units which are not installed in accordance with <br />_ipplicabie local codes, ordinances, or accepted trade practices, <br />and (E) to units repaired s,ndlor modified without prior authorization <br />from SJE-RHi`3MBUS�. <br />Check the floats during their entire range of operation. Cleary, <br />adjust, or replace damaged floats. <br />Checking the float resistance - The Moat resistance can be <br />measured to determine if the float is operating correctly or is <br />defective. Use the following procedure to measure the float <br />resistance. Warning: Disconnect all incoming power to panel. <br />Failure to do so could result in serious or fatal electrical shock. <br />1. isolate the float by disconnecting one or both of the float leads <br />from the float terminals. <br />2. Place one ohmmeter lead on one of the float wires, and the <br />other ohmmeter lead on the other float wire. <br />3. Place the ohmmeter dial to read ohms and place on the R X <br />1 scale. With the float in the "off' position, the scale should <br />read infinity (high resistance). Replace the float if you do not <br />get this reading. With the float in the ON position, the scale <br />should read nearly zero (very low resistance). Replace the <br />float if you do not get this reading. <br />NOTE: Readings may vary depending on the length of wire <br />and accuracy of the measuring device. <br />Fuses <br />Check the continuity of each fuse. With power OFF, pull the fuses <br />out of the fuse blocks. With the ohmmeter on the R X 1 scale, <br />measure resistance. A reading of infinity indicates a blown fuse <br />and must be replaced. Replace fuse with same type, voltage and <br />amp rating, <br />Magnetic COntaCIOF Coli <br />Warning: Disconnect all incoming power to panel. Failure to do <br />so could result in serious or fatal electrical shock. Check the coil <br />by disconnecting one of the coil leads. Measure the coif resistance <br />by setting the ohmmeter on the R X 1 scale. A defective coil will <br />read zero or infinity, indicating a short or opened coil respectively. <br />Replace defective contactor with same type. <br />Some states do not allover limitations on how long an implied warranty <br />lasts, so the above limitation may not apply to yore. Some states do <br />not allow the exclusion or limitation of incidental or consequential <br />damages, so the above limitation orexr1usion may not apply to you. <br />This warranty gives you specific: legal rights, and you may also have <br />other rights which var,r from state to state, <br />TO OBTAIN WARRANTY SERVICE: The consumer shall assume <br />all responsibility and expense for removal, reinstallation, and freight. <br />Any iters to be repaired or replaced under this warranty must be <br />returned to SJE-RHC MBUSO, or such place as designated by <br />SJE-RHOMBUS". <br />NOTICE! <br />Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees <br />will not be exposed to heath hazards in handling said material. All applicable laws and regulations shall apply. <br />