Laserfiche WebLink
im6ETTLFR-RYAN INC. FORM 1 GR Job # 22205358 <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GDF Name and Address GDF Representative and Title PHASE II SYSTEM TYPE <br /> Arco 7049 Vince Caulag (Check One) <br /> 800 E. Kettleman Ln. <br /> Lodi,CA 95240 GDF Phone No Balance 1/ <br /> 916-858-9907 Hirt <br /> Permit Conditions Source,GDF Vapor Recovery System Red Jacket <br /> CAS Hasstech <br /> Healy <br /> GDF# Other <br /> A/C# Manifolded7 Yes No <br /> Operating Parameters <br /> Number of Nozzles Served by Tank#1 16 Number of Nozzles Served by Tank#3 <br /> Number of Nozzles Served by Tank#2 16 Number of Nozzles Served by Tank t#4 <br /> Applicable Regulations: VR-203-1 and VR-204-1 VN Recommended <br /> Source Test Results and Comments <br /> Tank#: 1 2 3 4 <br /> 1. Product Grade <br /> 87 91 <br /> 2. Actual Tank Capacity, gallons 24970 11673 <br /> 3. Gasoline Volume Total <br /> 20287 4279 <br /> 4. Ullage,gallons (#2-#3) <br /> 12272 4683 7594 <br /> 5. Initial Pressure, inches H2O 2.00 <br /> 6. Pressure After 1 Minute, inches H2O 2.00 <br /> 7. Pressure After 2 Minutes, inches H2O 1.99 <br /> 8. Pressure After 3 Minutes, inches H2O 1.99 <br /> 9. Pressure After Minutes, inches H2O 1.98 <br /> 10. Final Pressure After 5 Minutes, inches H2O 1.97 <br /> 11. Allowable Final Pressure 1.87 <br /> Test Conducted by: Test Company: Date of Test: <br /> Darnell smith Gettler-Ryan Inc. 11/22/2022 <br /> California Air Resource Board March 17, 1999 <br /> TP-201.3, Page 14 <br />