E1.0LIGHTINGPLAN ANDSCHEDULEA.CONFIRM LIGHTING FIXTURE QUANTITIES WITH SUPPLIER.B.EMERGENCY AND NORMAL LIGHTING MARKED WITH "NL" SUBSCRIPT SHALL OPERATE CONTINUOUSLY. PROVIDEUNSWITCHED HOT TO NORMAL AND EMERGENCY BALLAST.C.EMERGENCY LIGHTING TO BE LEFT IN PLACE.D.ALL CONDUITS ENTERING OR LEAVING COOLER/FREEZER SHALL BE PROVIDED WITH SEAL-OFF FITTING WITHCOMPOUND PER NEC 300-(7a).E.ALL INTERIOR LIGHTING CIRCUITS TO BE WIRED THRU THE LIGHTING CONTROL RELAYS.F.CONTRACTOR TO FIELD VERIFY CEILING TYPE AND PROVIDE PROPER MOUNTING HARDWARE.G.ALL FIXTURES SUPPLIED WITH LAMPS.H.ALL LIGHTS SUPPLIED BY OWNER AND INSTALLED BY G.C.I.GC TO PROVIDE INDOOR & OUTDOOR LIGHTING MEASURES TO COMPLY WITH CA T-24 REQUIREMENTS PERLIGHTING MANDATORY MEASURES LABELED LTG-MM AS SPECIFIED ON SHEET T24'S. THESE INCLUDEAUTOMATIC CONTROL DEVICES, OVERRIDE SWITCH FOR BUILDING LIGHTING SHUT OFF, DAYLIGHT SWITCHES &LIGHTING CONTROL. ADJUST EXISTING CIRCUITING AS REQUIRED FOR COMPLIANCE. ALL EXTERIOR LIGHTS ANDSIGNAGE TO BE CONTROLLED VIA TIME CLOCK, "SUPPLIED BY THE GC IF NOT CURRENTLY EXISTING.µJ.PENDANT LIGHTS SHALL BE CENTERED OVER TABLES. VERIFY TABLE LOCATIONS WITH SEATING VENDORSUPPLIED CORE DRILL PLAN PRIOR TO LOCATING PENDANTS.K.DOWNLIGHTS IN BLACK DROPPED CEILING SHALL HAVE BLACK TRIM RINGS.L.ALL E2 & EM2 FIXTURES ARE NEW FIXTURES TO REPLACE EXISTING IN EXISTING LOCATIONS. ALL REPLACEDEMERGENCY FIXTURES SHALL BE REPLACED WITH SAME.M.ADJUST POSITION OF AIR SUPPLY DIFFUSERS ALONG WITH THE ASSOC. DUCT WORK.N.REPLACE OR REPAIR THE EXISTING AIR CONDITION SYSTEM SO THAT IT FUNCTIONS AS IT WAS ORIGINALLYDESIGNED OR BETTER, INCLUDING A RE-BALANCE.O.WHERE INDICATED, LIGHTING CONTROLLED VIA OCCUPANCY SENSORS, SEE SHEET E3.0.REPLACE ALL LIGHT FIXTURES (EXCEPT HOOD AND WALK-IN)RECOMISSION HVAC SYSTEM (REFURBISH AND REPLACE TO ORIGINAL SPECS)REMARKSTYPEVOLTMOUNTINGHT.WATTDESCRIPTIONMANUFACTURER / CATALOG NUMBERLOCATIONQUANTITYNO.LAMPTYPEC1B33DININGTCPB6IC-AT-W-LED14 / DR5630KB956" 30K 90CRI BLACK TRIM,W/ ELITE B6IC-AT-W 6"LEDRECESSED12014INCL1.ALL GENERAL LIGHTING WITHIN DAYLIGHT ZONES SHALL BESEPARATELY CONTROLLED FROM GENERAL AREA LIGHTING INCOMPLIANCE WITH SECTION 130.1(D) OF CEC BUILDING ENERGYEFFICIENCY STANDARDS.2.LINE DENOTING DAYLIGHT ZONE TYPICAL FOR ALL AREAS ADJACENTTO VERTICAL FENESTRATION WITH DIMENSIONAL CRITERIA ASFOLLOWS:DEPTH:-WINDOW HEIGHT INTO SPACE, OR TO NEAREST CEILINGHEIGHT OPAQUE PARTITION (WHICHEVER IS LESS).WIDTH:-WIDTH OF WINDOW PLUS ONE-HALF TIME WINDOW HEADHEIGHT ON EACH SIDE, OR WINDOW WIDTH PLUS DISTANCE TO OPAQUE PARTITIONS, OR WINDOW WIDTHPLUS ONE-HALF THE DISTANCE TO ADJACENT SKYLIGHTOR VERTICAL FENESTRATION (WHICHEVER IS LESS).3.PROVIDE CEILING MOUNTED DAYLIGHT SENSOR FOR EACHDAYLIGHT ZONE TO CONTROL GENERAL LIGHTING LUMINARIESWITHIN THE DAYLIGHT ZONE. LOCATION AND CALIBRATION OFSENSOR SHALL NOT BE READILY ACCESSIBLE TO UNAUTHORIZEDPERSONNEL AND SHALL BE CONFIGURED IN THE FIELD.4.PROVIDE CEILING MOUNTED OCCUPANCY SENSORS LOGISTICALLYLOCATED IN THE SALES AREA TO AUTOMATICALLY SHUT OFF ALLLIGHTING WHEN THE SPACE IS TYPICALLY UNOCCUPIED INCOMPLIANCE WITH SECTION 130.1(C) OF THE CEC BUILDINGENERGY EFFICIENCY STANDARDS.5.PROVIDE DIMMER SWITCHES COMPATIBLE WITH LIGHTING FIXTURESBEING INSTALLED. REFER TO FIXTURE SCHEDULE ONARCHITECTURAL SHEETS FOR MORE FIXTURE INFORMATION.DIMMERS SHALL BE EQUIPPED WITH MANUAL ON/OFF CAPABILITYFOR ALL SALES AREA LIGHTING IN COMPLIANCE WITH SECTIONS130.1 (A) AND (B) FOR AREA CONTROLS AND MULTI-LEVEL LIGHTINGCONTROLS OF THE CEC BUILDING ENERGY EFFICIENCY STANDARDS.FINAL LOCATION OF CONTROLS TO BE VERIFIED WITH KFCCONSTRUCTION MANAGER.DAYLIGHT ZONE-LIGHTING CONTROL KEYED NOTESTYPICAL LIGHTINGCONTROL DETAIL(NOT TO SCALE)KEYNOTE SYMBOL ON PLAN1.POWER AND DIGITAL CONNECTION FOR NEW DIGITAL MENUBOARDS. GC TO VERIFY LOCATIONS WITH STRATACACHE.2.EC SHALL INSTALL SHOW WINDOW RECEPTACLE IF NONEARE PRESENT. EC SHALL PROVIDE (1) 20A, 120V CIRCUITBACK TO SPARE CIRCUIT IN EXISTING PANEL BOARD. NEWCIRCUIT BREAKER SHALL MATCH TYPE AND RATING OFEXISTING BREAKERS.3.REINSTALL EXISTING FRONT COUNTER POWER AND DATACONNECTIONS. INCLUDE IN BID REINSTALLATION OF (3)DUPLEX OUTLETS, (2) QUAD OUTLETS, (7) 2"X4" J-BOX WITH3/4" CONDUIT FOR DATA/PHONE AND ALL ASSOCIATEDWIRING.4.PROVIDE PRIMARY DAYLIGHT ZONE SENSOR.5.PROVIDE SECONDARY DAYLIGHT ZONE SENSOR.6.LIGHT CONTROLLED BY MOTION SENSOR.7.EXISTING DIMMING SWITCH BANK WITH 2 HOUR BYPASS TOMEET TITLE 24 MANDATORY MEASURES - VERIFY IN FIELD8.NEW LED LIGHT BAND - WALL LIGHTING WITH FINISHEDBREAK METAL COVER AND TRANSFORMER. E.C. TOCONNECT TO EXISTING SIGN CIRCUIT.9.NEW BATTERY BACKUP EMERGENCY LIGHT FIXTURE.10.EXTERIOR WALL SCONCE. NEW FIXTURE REUSE (E)JUNCTION BOX AND CIRCUIT.11.EXISTING WALL PACK TO REMAIN.12.EXISTING ILLUMINATED EXIT SIGN TO REMAIN.13.NEW SIGNS - REUSE EXISTING SIGNS JUNCTION BOXES ANDCIRCUITS.14.NEW LED LIGHTS IN BACK OF HOUSE AND RESTROOMS.REUSE EXISTING CIRCUITS.15.NO WORK IN WALK IN BOXES.16.DAYLIGHT SENSOR. SEE LIGHTING CONTROL PLAN17.OCCUPANCY SENSOR. SEE LIGHTING CONTROL PLAN.#F64DININGHUB TABLEKICHLER 43852OZ9.75" GLASS PENDANT AVERY WITHOLD BRONZE FINISHLEDPENDANTSEEELEVS1206(1) AAMSCOLED-6W-ST64HYBRID-DIMF79DININGPENDANT LIGHTINGHI-LITES H24212-96-CB15-20WLBL-6OP12" GALVANIZED PENDANT W/ BLACKCORD AND CANOPY MED BASELEDPENDANTSEEELEVS12020(1) TCP LED10A19D0D27KB17KITCHENMAXLITEMLFP24G427WCS2x4 LED FLAT PANELLEDRECESSEDGRID12045-B1E4KITCHENMAXLITEMLFP24G427WCS2x4 LED FLAT PANELLEDSEEPLAN12045-E1W2DININGKITCHENLIGHT ALARMSEM-809-W2 HEAD EMERGENCYWHITELEDWALLSEEELEVS1205PROVIDED WITH 90 MIN.BATTERY PACKX1WEXISTINGDININGKITCHENEXISTING TO REMAINLIGHT ALARMSUNIVERSAL MNTG THERMOPLASTICEXIT, RED LETTERS-WHITELEDWALLSEEELEVS1202.8PROVIDED WITH INTEGRALBATTERY BACK UPSCSSMCMCSMWCCSSCCWOCOCB - 7bB - 7aC1BC1BF7B - 7aF6B - 7bF7B - 7aF7B - 7aF7B - 7aF7B - 7aB - 7aC1BB - 7aC1BB - 7aC1BB - 7aC1BB - 7aC1BB - 7bB - 7bB - 7bF6F6F6F7B - 7aB - 7aB - 7cB - 7dC2BC2BC2BB - 7cC1BB - 7cC1BB - 7dC1BB - 7dC1BB - 7dC1BB - 7cC1BB - 7aC2BB - 7aC1BB - 7bB - 7aC1BB - 7aC1BB - 7bC1BB - 7aC1BB - 7bC1BB - 7bC1BB - 7aC1BB - 7cC1BB - 7cC1BB - 7cC1BB - 7cC1BB - 7cC1BB - 7dC1BB - 7dC1BB - 7dC1BB - 7dC1BB - 7dC1BF7B - 7aF7B - 7aF7B - 7aB114B1EB1B1EB1B1B1EB1EB1B1B1B2B2B22RESTROOMS MAXLITE-1x4 LED FLAT PANELLEDSEEPLAN12045-C2B5DININGTCPB6IC-AT-W-LED14 / DR5630KB956" 30K 90CRI BLACK TRIM,W/ ELITE B6IC-AT-W 6"LEDRECESSED12014WITH FRESNELL LENSEC2B(IF REQUIRED)ALL OUTLETS AND BOXES MOUNTED IN THESERVING COUNTER CABINETRY ARE TO BE 24" AFF.INSTALL JUNCTION BOXES WITH CONDUIT UNDERCABINET TO NEAREST WALL AND TO ABOVECEILING.PROVIDE DEDICATED OUTLET FOR SAFE.E.C. SHALL PROVIDE A PREPRINTEDSELF-ADHESIVE LABEL ON ALL POS RECEPTACLESSTATING "POS USE ONLY".G.C. TO COORDINATE DIMENSIONS WITH OWNERSREPRESENTATIVES.HOLD-UP BUTTON (MOUNT 2-1/2"BEHIND COUNTER EDGE) + 16" A.F.F.J-BOX2" x 4" J-BOX W/ DATA PORTS +16" A.F.F.JDOUBLE DUPLEX ISOLATED GROUND OUTLETDUPLEX ISOLATED GROUND OUTLETmOCCUPATIONAL SENSOR + 44" A.F.F.(U.O.N.) TO CENTERLINE OF SWITCH DDIMMER SWITCHES +44" A.F.F. (U.O.N.) TO CENTERLINE OF SWITCH +16" A.F.F., U.O.N.+16" A.F.F., U.O.N.JJJJ5454FIRE SPRINKLER HEADSCSMB - 7cC1BB - 7dC1BX1WX1WE1WE1WREVISIONSALL IDEAS, DESIGNS, ARRANGEMENTS AND PLANS INDICATED BY THIS DRAWING ARE OWNED BY, AND THE PROPERTY OF THIS OFFICE AND WERE CREATED, EVOLVED AND DEVELOPED FOR USE ON, AND IN CONNECTION WITH, THE SPECIFIED PROJECT. NONE OF SUCH IDEAS, DESIGNS, ARRANGEMENTS OR PLANS SHALL BE USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF PROJECT ARCHITECT.WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALE DIMENSIONS: CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR, ALL DIMENSIONS AND CONDITIONS ON THE JOB AND THIS OFFICE MUST BE NOTIFIED OF ANY VARIATION FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS. SHOP DETAILS OF ADEQUATE SCALE MUST BE SUBMITTED TO THIS OFFICE FOR APPROVAL BEFORE PROCEEDING WITH FABRICATION ON ITEMS SO NOTED.W:\Data\Golden Gate Bell\21036_GGB_Tracy_STracyBlvd_30810\03_cd\_current\900_21036_E1-0_Lighting Plan.dwg By: GRENVILLE Saved on:3/18/2022 10:11:29 AM <br />RECORD DATESDD SUBMITTALBLDG. SUBMITTALBID SETCONTRACT SET-07/02/2021-VMI JOB NUMBER21036CLIENTGOLDEN GATE BELL3120 S. DURANGO DRIVELAS VEGAS, NV 89117Contact: Chris Czyz, (602) 714-3099SITE #30810PROJECTTACO BELL REMODEL915 S. TRACY BLVD.TRACY, CA. 95376APN #TBDENDEAVORSUCCESSOR637 5th Avenue San Rafael, CA 94901415-451-2500 415-451-2595 faxwww.vmarchitecture.comDesign ~ Planning ~ InteriorsN <br />IATAFOCTEOFLIRS L <br />TCEDDNo. C17928REN. 10/31/23UGHH <br />A MYHPURRRWDEAAI <br />E <br />C <br />NSECHTIREF.NORTH