Laserfiche WebLink
Scope of Work <br />Addendum to Permit #22 -3444 -modify drain system from <br />gravity flow to a pump system due to conflicts at the floor <br />level. <br />Instructions <br />The comments listed below require correction or clarification <br />before plans can be approved for permit issuance. Each line <br />item includes a comment and sheet number, if applicable, for <br />easy reference to the marked -up plans. Please resubmit all <br />revised plans using the same filename as the original submittal <br />unless otherwise noted. Thank you. <br />Building Safety <br />Page 3 1 Sheet P1.0 I Comment <br />00002 The plans are not clear as to whether the 1" discharge line <br />REv1-ARCH-Drain Pump -Permit 22- from the pump will be under slab or overhead. Clearly define <br />3444.pdf this and indicate where the pump will be located, is it sitting <br />+ Dale Hallock on the slab or is it under the slab? <br />+ 2094568571 <br />+ dhallock@ci.manteca.ca.us Show elevation drawings to clarify. <br />Response: The 1" discharge line from the pump is overhead. The pump will be <br />sitting on the slab. The discharge line will be placed within the wall to the attic <br />space above and then to a Floor Sink in the kitchen. Sheet #3 shows the <br />elevation at the pump and drain line. <br />Page 3 1 Sheet P1.0 I Comment <br />00001 Plans must clarify if 1" drain discharge is going into the <br />REv1-ARCHprain Pump -Permit 22- existing grease interceptor under pressure. <br />3444.pdf <br />Show the plumbing configuration as to how and where the <br />+ Dale Hallock discharge pipe is to be connected prior to going into the the <br />