My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2022
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
V
>
VALPICO
>
550
>
2300 - Underground Storage Tank Program
>
PR0536555
>
COMPLIANCE INFO_2022
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/6/2022 1:21:06 PM
Creation date
10/19/2022 8:05:44 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2022
RECORD_ID
PR0536555
PE
2351
FACILITY_ID
FA0020989
FACILITY_NAME
Arco. Am pm 83333
STREET_NUMBER
550
Direction
W
STREET_NAME
VALPICO
STREET_TYPE
Rd
City
Tracy
Zip
95376
CURRENT_STATUS
01
SITE_LOCATION
550 W Valpico Rd
P_LOCATION
03
P_DISTRICT
005
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
59
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: FDat,-.Arco.Am pm 83333 550 W Valpico Rd, Tracy ber 19, 2022 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 104 CCR 2632(d)(1), 2634(d)Failure to submit a complete and accurate UST Monitoring Plan. <br /> OBSERVATION: The monitoring plan is not current. The monitoring plan lists audible/visual and ball floats for all <br /> three tanks but ball floats were removed and flappers were installed 11/10/2021. <br /> REGULATION GUIDANCE: The monitoring plan must be uploaded to the California Environmental Reporting <br /> System (CERS). <br /> CORRECTIVE ACTION: This was corrected on site by submitting changes into CERS. <br /> This is a repeat violation, Class II. <br /> 107 HSC 25292.2; CCR 2711(a)(11)Failure to submit and maintain complete and current financial responsibility <br /> documents. <br /> OBSERVATION: Financial responsibility documents have not been submitted to the EHD. The most recent <br /> financial responsibility documents in CERS did not obtain new signatures and dates. <br /> REGULATION GUIDANCE: Current financial responsibility documents are required to be submitted annually. <br /> CORRECTIVE ACTION: This was corrected on site by submitting corrected documents into CERS. <br /> This is a repeat violation, Class II. <br /> 115 CCR 2638(c), 2638(d) Failure to submit"Monitoring System Certification Form"within 30 days of completion of the <br /> test. <br /> OBSERVATION:Annual monitoring system certification and leak detector testing was performed on 10/20/2021 and <br /> a test report was submitted on 12/5/2021, 16 days late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are <br /> performed in a timely manner. <br /> This is a minor violation. <br /> FA0020989 PR0536555 SCO01 10/19/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.