Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for TRACY SHELL as of May05 , 2023 . <br /> Open violations from January 30 , 2023 inspection <br /> ❑ This violation was corrected ❑ This violation will be corrected by ( date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Violation #319 - Failure to comply with overfill prevention equipment requirements . <br /> OBSERVATION Overfill prevention testing has not been conducted . Overfill prevention testing was last performed <br /> on 5/ 19/2019 and was due by 10/ 13/2021 <br /> REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October <br /> 13 , 2018 , and every 36 months thereafter, and within 30 days of completion of a repair. <br /> CORRECTIVE ACTION : Immediately schedule this testing and provide 48 hours notification to the EHD . <br /> ❑ This violation was corrected ❑ This violation will be corrected by ( date) . <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Page 6 of 6 <br />