Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-91-PS 2-87-PS 3-Dsl-PS 4-91-FRS <br /> Sump Manufacturer CSI CSI CSI CSI <br /> Sump Depth (inches) 64" 70" 65" 58" <br /> Sump Bottom to Top of 36" 19" 20" No Pipe <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:52 10:32 10:37 9:02 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:22 11:02 11:07 9:32 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID 5-87-FRS 6-Dsl-FRS UDC 1&2 UDC 3&4 <br /> Sump Manufacturer CSI CSI Western FG Western FG <br /> Sump Depth (inches) 63" 57" 29" 29 1/2" <br /> Sump Bottom to Top of No Pipe No Pipe 10" 10" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:07 9:12 10:17 9:17 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:37 9:42 10:47 9:47 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />