Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer ❑Q Industry Standard El Professional Engineer <br /> Test Type © Pressure Q Vacuum E Hydrostatic <br /> Test Equipment Used: OMNTEC - Proteus OEL8000111-CLD Series <br /> Sump/UDC ID 87-1 STP 87-2 STP 91 STP <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP) Unknown (FRP) <br /> Sump Depth (inches) 56 55 54 <br /> Sump Bottom to Top of 20 18 17 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:10 10:10 10:10 <br /> Initial Reading 11.215 12.274 13.667 <br /> Test End Time 10:25 10:25 10:25 <br /> Final Reading 11.215 12.275 13.667 <br /> Change in Reading 0.000 0.001 0.000 <br /> Pass Fail Criteria +/-0.002 +/-0.002 +/- 0.002 <br /> Tightness Test Results El Pass rl Fail © Pass rl Fail © Pass © Fail 0 Pass ❑l Fail <br /> Sump/UDC ID UDC#1-2 UDC#3-4 UDC#5-6 UDC#7-8 <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP) Unknown (FRP) Unknown (FRP) <br /> Sump Depth (inches) 30 30 30 30 <br /> Sump Bottom to Top of 15 15 15 15 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 14:45 14:45 12:53 12:53 <br /> Initial Reading 8.602 9.686 9.376 8.846 <br /> Test End Time 15:00 15:00 13:08 13:08 <br /> Final Reading 8.602 9.687 9.376 8.832 <br /> Change in Reading 0.000 0.001 0.000 -0.014 <br /> Pass Fail Criteria +/-0.002 +/-0.002 +/- 0.002 +/- 0.002 <br /> Tightness Test Results 0 Pass 0 Fail © Pass 0 Fail ©✓ Pass © Fail I! Pass L4 Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />