GENERAL NOTES Ar BREV�AT�ONS AND TAGS � ELECTRCAL LEGEND
<br /> ABB. DESCRIPTION ABB. DESCRIPTION SYMBOL DESCRIPTION ° . <
<br /> 9. GENERAL CONTRACTOR SHALL VERIFY FIELD CONDITIONS BEFORE SUBMITTING BID. 39. FOR ALL LIGHTING FIXTURES MOUNTED IN HUNG CEILING THE GENERAL CONTRACTOR SHALL PROVIDE
<br /> 2• ALL WORK SHALL HE DONE IN ACCORDANCE WITH NEC AS AMENDED BY CEC, AND ANY ADDITIONAL AND INSTALL INDIVIDUAL SUPPORT AT EACH CORNER OF RECESSED LIGHTING TROFFER CONNECTED TO AE APPROVED EQUIVALENT WP WEATHERPROOF
<br /> STATE OR LOCAL CODES WHICH MAY APPLY. BUILDING STEEL ABOVE ALL CONDUIT AND MC CABLE MOUNTED ABOVE HUNG CEILING SHALL HE $ SINGLE POLE SINGLE THROW SWITCH, +44" AFF U.O.N. X MEANS:
<br /> INDIVIDUALLY SUPPORTED IN THE SAFE FASHION AS PER NEC REQUIREMENTS. AFF ABOVE FINISHED FLOOR (E) EXISTING TO REMAIN
<br /> 3. GENERAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, CERTIFICATES, ETC. REQUIRED. EF EXHAUST FAN (N) NEW ® — CONTROLLING FIXTURE OR OUTLET "�"
<br /> ° NO DOUBLING UP" ON CIRCUIT BREAKERS OR CONDUCTOR SPLICES WITH IN PANEL BOARDS SHALL BE
<br /> ARCO
<br /> 4• GENERAL CONTRACTOR SHALL OBTAIN AND PAY FOR BOTH ROUGH AND FINAL UNDER—WRITERS OR OTHER PERMITTED. THE CONTRACTOR SHALL PROVIDE JUNCTION BOXES ADJACENT TO PANELBOARDS AS NTS NOT TO SCALE EC ELECTRICAL CONTRACTOR 2 — DOUBLE POLE
<br /> APPROVED INSPECTION AGENCY CERTIFICATES "ELECTRICAL INSPECTION°'. THESE CERTIFICATES SHALL BE REQUIRED TO SPLICE COMMON CIRCUITS CONNECTORS. PROVIDE FURNISH, INSTALL AND CONNECT. MC MECHANICAL CONTRACTOR 3 — THREE WAY
<br /> PRESENTED WITH REQUEST FOR FINAL PAYMENT. GFCI GROUND FAULT CKT. INTERRUPTER GC GENERAL CONTRACTOR D — DIMMER (RATING AS REQUIRED)
<br /> 5• IT IS THE INTENT OF THESE PLANS TO PROVIDE A COMPLETE OPERATING ELECTRICAL SYSTEM. THE 41° DO NOT SCALE FROM THESE DRAWINGS. AC MECHANICAL UNIT TAG. SEE
<br /> CONTRACTOR SHALL FURNISH AND INSTALL ALL WIRING, EQUIPMENT, MATERIAL. ETC, REQUIRED, EXCEPT 42. PLANS ARE PREPARED WITH REQUIRED BRANCH CIRCUITS INDICATED BY CIRCUITS NUMBERS. PROVIDE SMD SEE MECHANICAL DRAWINGS 1 MECHANICAL DRAWINGS FOR LOW VOLTAGE SWITCH FOR LIGHTING CONTROL PANEL
<br /> ERE SPECIFICALLY NOTED AS BEING FURNISHED BY OTHERS. SHOULD THERE BE ANY QUESTIONS UAC UNDER ANOTHER CONTRACTADDITIONAL REQUIREMENTS. Y DOUBLE OR THREE POLE HP RATED TOGGLE SWITCH
<br /> AND INSTALL ALL CONDUITS. CONDUCTORS, BOXES, MISCELLANEOUS FITTINGS, ETC. FOR A COMPLETE
<br /> CONCERNING RESPONSIBILITY, THEY SHALL BE ADDRESSED TO ARCHITECT PRIOR TO BID. NO EXTRA AND OPERABLE SYSTEM (HOME RUN SHOWN). BRANCH CIRCUIT INSTALLATION SHALL COMPLY WITH LION UNLESS OTHERWISE NOTED E—� DETAIL TAG. REFER TO DETAIL 4
<br /> CHARGES WILL BE ALLO D• SPECIFICATIONS AND N.E.C. (R) (E) TO BE REMOVED 4 ON SHEET NUMBER E-4• SWITCH OCCUPANCY SENSOR WITH MANUAL ON/OFF OVERRIDE BUTTON
<br /> 6° ELECTRICAL SERVICE SHALL BE COORDINATED WITH THE EXISTING FIELD CONDITIONS. SPECIFICATIONS
<br /> IN COMPLIANCE WITH STATE TITLE 24 ACCESSIBILITY REQUIREMENTS, 406.3(G), THE BOTTOM OF RECEPTACLE (RL) (E) TO BE RELOCATED EQUIPMENT UNIT TAG, G PHOTOCELL FOR DAYLIGHT ZONING
<br /> 7• CONSULT WITH CONTRACTORS FURNISHING HVAC EQUIPMENT AND REFRIGERATION TO VERIFY LOADS AND OUTLETS SHALL NOT BE LESS THAN 15"AFF° THE TOP OF SWITCHES AND OTHER DEVICES SHALL BE NOT MORE (RR) (E) TO BE REMOVED AND REINSTALLED SEE EQUIPMENT SCHEDULE.
<br /> SECURE EXACT LOCATIONS (REFER TO HVAC DRAWINGS). WIRE AND CONNECT TO ALL HVAC EQUIPMENT. THAN 48"AFF OR 44"AFF IF REACHING OVER OBJECT EXCEEDING 20" DEEP, g SMOKE DETECTOR
<br /> INCLUDING CONTROLS AND THERMOSTATS. LCP LIGHTING CONTROL PANELELECTRICAL LIGHTING EQUIPMENT
<br /> 44• NATIONALLY RECOGNIZED TESTING LABORATORY SHALL LIST ALL EQUIPMENT IN COMPLIANCE NTH NEC ART. 110.3° FA—] UNIT TAG/TYPE ® DIMMER, ACCESSIBLE TYPE CONTROL COMPATIBLE WITH FIXTURE
<br /> 8° CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO ALL CONTROLS, Orli ER—SUPPLIED EQUIPMENT,
<br /> SEE LIGHT FIXTURE SCHEDULE. BALLAST IN USE
<br /> MECHANICAL AND PLUMBING EQUIPMENT AS REQUIRED, DUPLEX RECEPTACLE 20A, 125V, NEMA 5-20R MALL MOUNTED.
<br /> 9° REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATION DETAILS. ALL FIXTURE AND DEVICE LOCATIONS 45• ALL EQUIPMENT LISTED IN SCHEDULES SHALL BE PRODDED WITH REQUIRED POWER CONNECTION, U.O.N. (WP= WEATHERPROOF, D= DEDICATED, GFI=GROUND FAULT
<br /> SHOWN ON ARCHITECTURAL DRAWINGS SUPERSEDE THOSE SHOWN ON ELECTRICAL PLANS. INTERRUPTER)
<br /> 10° CIRCUIT NUMBER ON THE DRAWINGS ARE FOR IDENTIFICATION ONLY AND DO NOT INDICATE THE POSITION 46° ELECTRICAL CONTRACTOR SHALL FOLLOW LOCK OUT/TAG OUT PROCEDURE PER CAL—OSHA STANDARDS DURING GHADUPLEX RECEPTACLES 20A, 125V, NEMA 5-20R HALF SWITCHED. O
<br /> ON THE PANEL BOARD. CONNECT THE CIRCUITS WITH THE LIGHTEST LOADS AND THE RECEPTACLE CONSTRUCTION.
<br /> CIRCUITS NEAR THE TOP OF THE PANEL, AND THE MORE HEAVILY LOADED CIRCUITS NEAR THE BOTTOM. 46° DUCT DETECTORS SHALL BE CONNECTED TO THE FIRE ALARMI SYSTEM TO INITIATE SUPERVISION° THE DUCT DOUBLE DUPLEX RECEPTACLES, NEMA 5-20R°
<br /> BALANCE ALL CIRCUITS EVENLY BETWEEN PHASE SO THAT FEEDER WIRES CARRY APPROXIMATELY EQUAL '�
<br /> DETECTORS SHALL REQUIRE AN ACCEPTANCE FUNCTION TEST AND TEST SHALL BE WITNESSED BY THE INDIO FIRE CEILING DUPLEX RECEPTACLE 20A, 125V, NEMA 5-20R
<br /> CURRENT. ALL PHASES MUST BE BALANCED WITHIN 10% OR LESS° G.C. SHALL REBALANCE IF NECESSARY. DEPARTMENT FOR AUTOMATIC SHUTDO • TESTING SHALL BE IN ACCORDANCE NTH NFPA 72 2002 EDITION AND
<br /> 11° BRANCH CIRCUIT CONDUCTORS SHALL NOT BE LESS THAN M, 2AWG. THE INSULATION SHALL BE COLOR
<br /> MANUFACTURER'S INSTRUCTIONS. ALL SUBCONTRACTORS SHALL BE PRESENT HVAC, FIRE ALARM AND ELECTRICAL. (WP= WEATHERPROOF, D= DEDICATED, GFI=GROUND FAULT
<br /> CODED. AND SHALL BE 500 VOLT. TYPE THHN/THWN COPPER. INTERRUPTER) ® _
<br /> DOUBLE DUPLEX RECEPTACLES, NEMA 5-20R° (FLOOR MOUNTED)
<br /> 12• CABLES IN HIGH TEMPERATURE AREAS SHALL HAVE INSULATION TYPE SUITABLE FOR THE TEMPERATURE°
<br /> C
<br /> CABLES USED IN SPACES FOR ENVIRONMENTAL AIR SHALL CONFORM WITH APPLICABLE N•E°C SPECIAL RECEPTACLE, RATING AS SHOWN. O ENO\ ��
<br /> REQUIREMENTS.
<br /> 13° ALL WIRING USED IN RETURN OR DISCHARGE AIR PLENUMS SHALL BE PLENUM RATED OR INSTALLED PER JUNCTION OR OUTLET BOX
<br /> METHODS APPROVED BY THE LATEST EDITION OF THE N.E.C. FOR SUCH APPLICATION. WALL MOUNTED JUNCTION BOX 18215 72ND AVENUE SOUTH
<br /> 14• ALL WIRE AND CABLE CONDUCTORS SHALL BE COPPER WITH INSULATION RATED 60OV. CONDUCTORS KENT, WA 98032
<br /> SIZED #10 AWG AND SMALLER SHALL BE SOLID, AND CONDUCTORS SIZED LARGER THAN #10 AWG SHALL 3z (3) CAT-5 DATA OUTLETS. PROVIDE OUTLET BOX AND (425)251-6222
<br /> BE STANDARD WIRE. COVERPLATE WITH CABLING TO TERMINATION POINT. (425)251-8782 FAX
<br /> 15° BRANCH CIRCUITS FOR POWER AND LIGHTING SHALL NOT BE LESS THAN #12 AWG. OR AS NOTED. WIRES DJ FUSED DISCONNECT SWITCH, RATING AS SHOWN
<br /> ARE TO BE SIZED FOR THE APPROPRIATE VOLTAGE DROPS. CIVIL EN�tld tNG, LAND PIIt�tHG,
<br /> SIJ tGI, ENRONMMTAL SERWCES
<br /> 16• ALL EQUIPMENT AND LIGHT FIXTURES WIRING SHALL NOT BE LESS THAN X12 AWG TYPE SFF-2• AND
<br /> NON FUSED DISCONNECT SWITCH, RATING AS SHOWN
<br /> FLEXIBLE CORDS SHALL NOT BE LESS THAN #12 AWG TYPE S.
<br /> M MOTOR OUTLET AND FLEX CONNECTION TO MOTOR. NO. DAA REVISION DESCRIP71ON
<br /> 17° CONTROL WIRING SHALL NOT BE LESS THAN #14 AWG UNLESS OTHERWISE NOTED. 1.18.15 PERMIT SUBMITTAL
<br /> _ ElLV INGROUND TRANSFORMER
<br /> 18• HOMERUNS SHOWN ARE SCHEMATIC. CONTRACTOR MAY ORIGINATE HOMERUNS FROM DIFFERENT
<br /> LOCATIONS. ALL WIRE INCLUDING HOMERUNS SHALL BE DELINEATED ON AS—BUILT DRAWINGS. FLEXIBLE CONDUIT WITH CONNECTION TO EQUIPMENT
<br /> 19• ALL WIRING INSTALLED UNDER THIS CONTRACT SHALL BE TESTED FOR PROPER CONNECTIONS AND SHORT . PANELBOARD/LOAD CENTER, SURFACE, FLUSH. �
<br /> CIRCUITS PRIOR TO THE TURNING OVER OF WORK AS A COMPLETE UNIT.
<br /> 20• PROVIDE ALL ELECTRICAL SYSTEM GROUNDING IN ACCORDANCE WITH N.E.C. REQUIREMENTS EVEN IF IT IS ORRANWA�CIRCUIT WIRING IN CONDUIT CONCEALED IN CEILING §
<br /> NOT SHOWN ON THE DRAWINGS. INCLUDE ADDITIONAL GROUNDING CONDUCTORS IN NONMETALLIC BRANCH CIRCUIT RING IN CONDUIT CONCEALED UNDER FLOOR OR
<br /> RACEWAYS EVEN THOUGH THE DRAWINGS SHOW ONLY CIRCUIT AND/OR NEUTRALS CONDUCTORS. THE —a®® UNDERGROUND.
<br /> PLUMBING AND PIPING SYSTEM SHALL NOT BE USED AS A GROUND. ALL TRANSFORMER NEUTRALS SHALL
<br /> BE GROUNDED TO BUILDING STEEL IN ACCORDANCE WITH NEC 250-70° 20 AMPS, 120V LTG RECEPTACLE CIRCUITS BRANCH CIRCUIT HOMERUN TO PANEL. �
<br /> 21• ALL CONDUITS PASSING THROUGH PARTITIONS ARE TO BE APPROPRIATELY SLEEVED AND SEALED. CONDUIT UP.
<br /> DISTANCE V31RE SIZE
<br /> 22• FURNISH AND INSTALL ALL CONDUIT WITH PULL WIRES AS REQUIRED. ALL OUTLET BOXES SHALL BE
<br /> ® CONDUIT DOWN.
<br /> STEEL, EXTRA DEEP WITH GROUNDING PIGTAILS. GROUNDING PUSH—CLIPS ARE NOT ACCEPTABLE. 1' TO 100° §12 AWG FLEXIBLE CONDUIT
<br /> 23• ALL SLAB PENETRATIONS SHALL BE INSTALLED AND FIRE RATED PER NATIONAL STATE AND LOCAL CONDUIT STUBBED OUT IN ACCESSIBLE LOCATION, CAP ANDSEAU
<br /> CODES 101' — 150' 10 AWG
<br /> 24° DO NOT MAKE ANY CHANGES OR SUBSTITUTIONS WITHOUT SPECIFIC WRITTEN APPROVAL FROM THE MARK LOCATION.
<br /> ARCHITECT OR ENGINEER. 151' — 200' §10 AWG ��� F sr
<br /> fl ��
<br /> 25. GUARANTEE ALL WORK, MATERIAL AND EQUIPMENT FOR A PERIOD OF ONE YEAR FROM THE DATED OF 2O1' — 25O' AWG
<br /> APPROVAL AND FINAL ACCEPTANCE.
<br /> o
<br /> 26. THIS DESIGN IS BASED ON INITIAL DESIGN DATA. GENERAL CONTRACTOR TO SUPPLY AND INSTALL 251® — 300' #3 AWG E17015 p�
<br /> FEEDERS, FUSES AND CIRCUIT BREAKERS TO MATCH THE NAMEPLATE RATING OF ALL EQUIPMENT. THIS8
<br /> + I.0 a°
<br /> SHALL BE INCLUDED IN THE INITIAL BID PROPOSAL AND NO EXTRAS SHALL BE ENTERTAINED. 301' UP ��AWG � o mo, 00�Q
<br /> 27° THE G.C. SHALL PROVIDE ALL EQUIPMENT. MATERIALS AND LABOR TO COMPLETE ALL ELECTRICAL WORK P©00000©
<br /> IN A NEAT AND WORKMANLIKE MANNER AND IN ACCORDANCE WITH GOOD COMMERCIAL PRACTICE
<br /> INCLUDING THE INSTALLATION OF ALL THE EQUIPMENT MATERIALS AND SYSTEMS AND THE FINAL
<br /> CONNECTIONS TO THE OWNER'S EQUIPMENT AND FIXTURES AS REQUIRED BY THE OWNER. THE G.C.
<br /> SHALL ALSO FURNISH TEMPORARY WIRING AND LIGHTING TO PROVIDE A MINIMUM OF 25 FC IN WORK
<br /> AREAS FOR USE OF ALL THE TRADES DURING CONSTRUCTION AND THE INSTALLATION OF THE OWNERS
<br /> UNE CONDUCTOR SIZE IS INCREASED TO COMPENSATE FOR VOLTAGE DROP. GROUND CONDUCTOR
<br /> FIXTURES. THE G.C. IS RESPONSIBLE TO REMOVE ALL TEMPORARY WIRING UPON COMPLETION OF SIZE SHALL BE INCREASED PROPORTIONATELY V4TH THE LINE CONDUCTOR PER NEC 250.122(8) � � �� B � ���
<br /> CONSTRUCTION OF ALL TRADES.
<br /> 28° G.C. SHALL LABEL ALL JUNCTION BOX, OUTLETS, LIGHT SWITCH, ETC. WITH CIRCUIT NUMBER ON
<br /> INTERIOR OF COVER PLATE. SHEET NUMBER DESCRIPTION
<br /> 29. GENERAL CONTRACTOR SHALL PROVIDE SEISMIC RESTRAINTS AND SUPPORTS FOR ALL FLOOR AND
<br /> CEILING MOUNTED ELECTRICAL EQUIPMENT TO RESIST EARTHQUAKE EFFECTS DETERMINED IN
<br /> ACCORDANCE WITH THE BUILDING CODE. EOA LEGEND, NOTES & SCHEDULES DEVELOPMENT INFORMATION:
<br /> 30° THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE AND INSTALL ALL SUPPLEMENTARY SUPPORT, EO.2 SPECIFICATIONS ARCO NT11
<br /> INCLUDING SUPPORT STEEL AS REQUIRED TO HANG ALL EQUIPMENT AND LIGHTING FROM THE
<br /> STRUCTURE IN ACCORDANCE WITH THE ARCHITECTURAL/STRUCTURAL SUPPORT AND LOADING CRITERIA. EO.3 TITLE 24 FORMS — INDOOR LIGHTING PART 1 3000 am/pm/ QSR
<br /> 31• IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE FULLY DIMENSIONED COORDINATION EO.4 TITLE 24 FORMS — IND R LIGHTING PART 2
<br /> DRAWINGS FOR ALL OF HIS RESPECTIVE WORK. THESE DRAWINGS MUST BE FULL COORDINATED WITH ALL FUEL CANOPY
<br /> CONDITIONS, ALL HVAC, PLUMBING, FIRE PROTECTION, ELECTRICAL, LIGHTING, STRUCTURAL AND EO.5 TITLE 24 FORMS — OUTDOOR LIGHTING PART 1
<br /> ARCHITECTURAL SYSTEMS PRIOR TO PREPARING COMPOSITE MULTI DISCIPLINE COORDINATION DRAWINGS.
<br /> 32° ALL DISCONNECTING MEANS AND EQUIPMENT INDICATED ON THE DRAWING SHALL BE IDENTIFIED BY NAMEPLATE IN EO°6 TITLE 24 FORMS — OUTDOOR LIGHTING PART 2
<br /> COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE 110-22• SITE
<br /> ADDRM-
<br /> 33. ALL WIRING FOR THE EMERGENCY LIGHTING AND EMERGENCY SYSTEMS SHALL BE INSTALLED IN ACCORDANCE NTH E1°0 LIGHTING PLAN ESCALON AVENUE
<br /> THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE ARTICLE 700° E2°0 POWER & LIGHTING SITE PLAN
<br /> @ HIGHWAY 120
<br /> 34° THE WIRING METHODS AND MATERIALS INDICATED IN THE SPECIFICATIONS AND ON THE DRAWINGS SHALL BE E2°1 POWER PLAN ESCALON,CALIFORNIA,
<br /> INSTALLED AND CONNECTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE ARTICLE
<br /> 300° E3°O ELECTRICAL ROUGH—IN PLAN
<br /> FACW`II V # 7SO
<br /> 35. THE ELECTRICAL SER\ICE AND DISTRIBUTION SYSTEM AS INDICATED ON THE RISER DIAGRAM AND E4<0 ELECTRICAL ROOF PLAN .
<br /> MATERIALS INDICATED IN THE SPECIFICATIONS SHALL BE IN COMPLIANCE WITH THE REQUIREMENTS OF A b 0 S S e I Fl
<br /> THE NATIONAL ELECTRIC CODE ARTICLE 230• E5.0 COMMUNICATION PLAN 0B=T. Tp T
<br /> 36• ALL GROUNDING REQUIREMENTS OF THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM AND AS INDICATED IN THE E5°1 DIAGRAM eke DETAILS — PART 1 Engineering ® °
<br /> SPECIFICATIONS SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250• L.
<br /> C.
<br /> E5°2 DIAGRAM DETAILS — PART 2L. ����
<br /> 37° ALL OVER CURRENT PROTECTION SHALL BE IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE SECTION 240°
<br /> E6°0 SINGLE LINE DIAGRAM DRAWING Tine
<br /> 38° PRIOR TO ANY REQUIRED CUTTING AND PATCHING OF CONCRETE FLOOR AND/OR CUTTING OF ROOF CONTRACTOR E6.1 ELECTRICAL PANEL SCHEDULES MECHANICAL — ELECTRICAL
<br /> SHALL COORDINATE WITH BUILDING ENGINEER. SEAL ALL EXTERIOR AND FIREWALL PENETRATIONS. CIVIL_ - LEED L
<br /> E6°2 ELECTRICAL PANEL SCHEDULES FIRE PROTECTION