Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for MANTECA LIQUOR & FOOD as of January 09, 2023. <br /> Open violations from April 25, 2022 inspection <br /> Violation#104-Failure to have an approved UST Monitoring Plan. <br /> OBSERVATION: The monitoring plan is not current and/or not approved by the EHD. <br /> -The monitoring plan for 87 tank incorrectly list the leak detector model as"Red Jacket".The leak detectors on site <br /> is 99LD2000. <br /> -The monitoring plans for both tanks incorrectly list the monitoring panel for the tank, piping, and UDC monitoring as <br /> a TLS 350.The panel on site is a TLS 350 Plus. <br /> REGULATION GUIDANCE: The monitoring plan must be uploaded to the California Environmental Reporting <br /> System (CERS). <br /> CORRECTIVE ACTION: Immediately log into CERS, make the necessary changes, and submit for review by the <br /> EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#106-Failure to submit and maintain a current facility plot plan/site map. <br /> OBSERVATION:An accurate UST Monitoring Site Plan was not submitted. <br /> -The site map did not include an annular sensor on the 91 tank. <br /> REGULATION GUIDANCE:A site plan must be submitted identifying the locations where monitoring will be <br /> performed. The site plan must show the general layout of tanks and clearly identify locations of the following <br /> equipment, if installed: 1)monitoring panels; 2)in-tank liquid level probes(if used for leak detection); 3)devices <br /> monitoring tank annular spaces or vault; 4)devices monitoring product piping; 5)devices monitoring fill piping; 6) <br /> devices monitoring vent piping; 7)devices monitoring vapor recovery piping; 8)devices monitoring vent/transition <br /> sumps; 9)devices monitoring under-dispenser containment; 10)line leak detectors; and 11)devices monitoring any <br /> other secondary containment areas. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov/and upload a copy of the UST Monitoring Site Plan. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 1 of 4 <br />