Laserfiche WebLink
JONES COVEY GROUP, INC* <br /> COMPLETE FUEL SYSTEM CONSTRUCTION €t MAINTENANCE SERVICES <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Costco 558 Tracy DATE: 1 2 16 2 0 2 2 <br /> State Facility# CONTACT: Site Supervisor <br /> 3250 W. Grantline Rd,Tracy Ca 95304 PHONE: (209)834-1247 <br /> JOB#: 2258851-1 <br /> Tank # T1: 87A T2: 87B T3: 87C T4: Gas Add <br /> Product Unleaded Unleaded Unleaded Unleaded Additive <br /> LD Manufacturer Veeder-Root Veeder-Root Veeder-Root Veeder-Root <br /> LD Model 0848480-001 0848480-001 0848480-001 0848480-001 <br /> Sump Condition Good Good Good Good <br /> Operation Pressure 37 psi 38 psi 42 psi 30 psi <br /> PSI <br /> Opening Time(Sec) N/A N/A N/A N/A <br /> Metering Pressure <br /> N/A N/A N/A N/A <br /> (PSI) <br /> Functional Element <br /> Holding Pressure 30 psi 28 psi 35 psi 22 psi <br /> Leak Rate LD Detected <br /> (GPH) 3.00 GPH 3.00 GPH 3.00 GPH 3.00 GPH <br /> Does LD Detect 3 GPH Yes Yes Yes Yes <br /> Leak Rate? <br /> LD Serial Unknown Unknown Unknown Unknown <br /> Comments: <br /> All PLLD's Passed testing at this time. <br /> Technician License Number VMI -4822 <br /> Signature <br /> 9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA, CA 91730- LICENSED IN 41 STATES <br /> California State License#804431 A, B, HAZ <br />