• Verification of leak monitoring communication for all installed vacuum, pressure, or hydrostatic (VPH) <br /> components including piping, sumps, under dispenser containment sumps (UDCs), and all chase <br /> lines. Communication at end points of each vacuum zone and each vacuum monitored sump must be <br /> verified independently in operating condition. <br /> • Verification of the dispenser footprints contained by the UDCs. Any potential leaks from piping and fuel <br /> filters must drain directly into UDCs. <br /> • Verification of VPH components installation (shroud boots and band clamps for spill containers, <br /> appropriate rubber-type gasket or clamps on lids on all fill, vent and STP sumps, etc.). <br /> • Verification of overfill prevention: Measurement of drop tubes to verify 95% tank volume shut off and/or <br /> verification that external audible/visual alarm activates when tank is 90% full. <br /> • Spill bucket test: Verify minimum 5-gallon capacity and pass a one hour hydrostatic test (or equivalent). <br /> Proper drainage method must be verified. <br /> • Monitoring system functionality: Functionality of the monitoring system must be verified to ensure it <br /> meets the requirements of California Code of Regulations (CCR)Title 23 and California Health & Safety <br /> Code (HSC) Chapter 6.7. <br /> ELD will be completed (tentatively) on 8-25 and will be submitted for review as soon as reasonably possible. <br /> Dates may be merged depending on testing company. <br /> Respectfully, <br /> �o6elf� ���a��cum <br /> Project Superintendent <br /> 909-276-0789 <br /> jmalcolm@ionescovey.com <br /> ►,� JCIN ESCOVEY GROUP,INC. <br /> This e-mail and any files transmitted with it are the property of Jones Covey Group,Inc are confidential,and are intended solely for the use of the individual or entity to whom this e-mail is addressed. <br /> 3 <br />