Laserfiche WebLink
Providers for MDleak® MSleak® DPleak®, MCleak® and <br />PHDleak® Testing Technologies <br />Page 1 of 4 <br />Test Type: Job #: 5116 <br />Facility Name: PO #: <br />Prepared For: <br />Site Address: <br />City: <br />State and Zip: CA 95337 <br />Start Date:End Date: <br />SYSTEM Test MDL TK-1 87 TK-2 91 TK-3 DSL <br />Product Primary MDleak:0.005 GPH PASS PASS PASS <br />Product Secondary:0.1 GPH PASS PASS PASS <br />Vent Primary MDleak:0.005 GPH PASS PASS PASS <br />Vent Secondary:0.1 GPH PASS PASS PASS <br />VR Primary MDleak:0.005 GPH PASS PASS NA <br />VR Secondary:0.1 GPH PASS PASS NA <br />MCleak Tank:0.005 GPH PASS PASS PASS <br />Turbine Sump Fittings:0.005 GPH PASS PASS PASS <br />Fill/Vapor Sump Fittings:0.005 GPH PASS PASS PASS <br />UDC Fittings:0.005 GPH PASS PASS PASS <br />Fill Bucket:0.1 GPH PASS PASS PASS <br />Vapor Bucket:0.1 GPH PASS PASS NA <br />Vent Box Fittings 0.005 GPH PASS PASS PASS <br />Fill Spill Bucket Hydro:0.1 GPH PASS PASS PASS <br />Vapor Bucket Hydro:0.1 GPH PASS PASS NA <br />Atherton Drive & Union Road <br />Manteca <br />6/6/20236/5/2023 <br />Jones Covey Group Inc. <br />Facility Certification CONFIDENTIAL <br />California ELD New Construction Test <br />Chevron