Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> Annular failed with a steady leak rate ,will need further investigation. Fill Sump passed hydrostatic testing. Unable to hydrostatic test <br /> piping sump due to vent test boot and penetration needing repair. Current boot and penetration is an all-in-one. Pipe measures 3.5x2.4. <br /> Will need IT bravo penetration for repair and a 3.5x2.4 SA test boot. Supply and return passed pressure testing. Recommend new <br /> view ports for piping sump as current cam locks are welded and cant be tightened/loosened. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />