Ili TAIT <br />701 N. Parkcenter Drive, Santa Ana, CA 92705 11.1.4 111 1.111 t•••14.1 <br />13;714/560/C222 www.tait.com <br />Identification of Test Procedures for Secondary Containment Testing <br />To Whom It May Concern: <br />Tait Environmental Services, Inc., utilizes the following procedures when conducting Secondary <br />Containment Testing: <br />Containment Sumps, Transition Sumps, UDCs — Tait follows PEI-RP1200-17 Section 6.6 for the <br />accelerated test method. Tait uses the Incon TS-1000 hydrostatic test equipment following the <br />attached procedures. <br />Spill Buckets; Direct Bury & Contained in Sumps — Spill buckets contained in sumps are tested <br />per PEI-1200-17, Section 6.2, however Tait Pass/Fail threshold is 0" drop in one hour. Direct Bury <br />Spill Buckets are test the same as containment sumps per PEI-1200-17, Section 6.6. <br />Tank Annular Space — testing is conducted per PEI-1200-17, Section 4.2 <br />Piping Secondary Containment — Testing is conducted per PEI-RP1200-17, Section 5.3 <br />Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br />Testing in lieu of either parts or the whole RP1200 document due to copyright infringement.