Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-Diesel-PS 3-91-PS <br /> Sump Manufacturer Western FG Western FG Western FG <br /> Sump Depth (inches) 39 1/2" 39 1/2" 39 1/2" <br /> Sump Bottom to Top of 11" 11" 11" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:42 10:47 11:32 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 11:12 11:17 12:02 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Bennett Bennett Bennett Bennett <br /> Sump Depth (inches) 29" 30" 29" 29" <br /> Sump Bottom to Top of 14" 15" 16" 17" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:52 10:57 11:37 11:42 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 11:22 11:27 12:07 12:12 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />