Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> DIAMOND GAS AND FOOD MART 824 E YOSEMITE AVE, MANTECA June 01, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 214 CCR 2712 Failure to comply with UST operating permit conditions. <br /> OBSERVATION: The facility is not in compliance with the written conditions of the operating permit. Service <br /> request#SR0084269 was approved on 10/29/2021 to convert the 89(mid grade)tank to diesel. Bio diesel 20 was <br /> observed on site and not diesel. <br /> REGULATION GUIDANCE: The owner and operator of underground storage tank(UST)systems shall comply with <br /> all requirements of the permit issued for the operation of the UST system. <br /> CORRECTIVE ACTION: Immediately take all necessary actions to bring these UST systems into compliance. <br /> This is a minor violation. <br /> 302 CCR 2630(d), 2641(a)Leak detection equipment not installed/maintained/located to detect leaks at earliest <br /> opportunity. <br /> OBSERVATION: The diesel STP sensor was raised approximately six inches off the lowest point of the sump <br /> saddle of the tank and not located to detect a leak at the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: The sensor was relocated to the lowest point of the sump by the service technician. <br /> Ensure that all monitoring equipment is maintained and located to detect a leak at the earliest opportunity. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> 306 HSC 25291(e)Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the 87 and diesel STP sumps. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed approximately 2cups of liquid from the 87 and diesel STP <br /> sumps. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a repeat violation, Class Il. <br /> FA0003677 PR0231459 SCO01 06/01/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 8 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />