Laserfiche WebLink
/ g 7 -s� <br /> E <br /> Measure&record"A"and'Z,"and then peform the following calculation: <br /> "A" n " Drop tube seal surface to the bottom of the tank <br /> -(subtract) <br /> "Z" • " Upper drop tube flange to the edge of the upper tube adapter <br /> -(subtract) <br /> 4.5" Reference offset <br /> _ (equals) <br /> 1 92- " Final shutoff volume height <br /> Locate the final shutoff volume <br /> height on the tank chart <br /> Use the tank chart provided by the tank provided by the tank <br /> manufacturer to record and calculate the following: manufacturer,and record the <br /> closest corresponding volume. <br /> gal Final shutoff volume <br /> (divide )by) `' <br /> 1 S L gal Actual tank capacity <br /> X(muliply by) <br /> 100 <br /> (equals) If the final shutoff volume <br /> o . o percentage is 95%or less,the <br /> Final shutoff volume percentage installation conforms to FFS and <br /> Lindustry recommended practices. <br /> © gal Actual tank capacity <br /> -(subtract) The final Shutoff Volume Percentage may <br /> be greater than 95%as long as the ullage <br /> gal Final shutoff volume volume remaining is greater than or <br /> _(equals) equal to 250 gallons,so that"...none of <br /> the fittings located on the top of the tank <br /> g8t Uliage volume remaining are exposed to product due to <br /> overfilling,"according to EPA 40 CFR Part <br /> 280. The installation must also meet all <br /> applicable regulatory requirements,and <br /> must be acceptable to the Authority <br /> Having Jurisdiction(AHJ). <br /> 8? tJ <br /> �'•-t - 33 <br /> 17 <br /> . s <br />