Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2361905 Date: 5/30/2023 <br /> Site Name/ID. Rebel Store#0375/375 <br /> Address: 2375 W Grant Line Road <br /> City: Tracy State: CA Zip: 95377 <br /> Tank ID REGULAR 87 REGULAR AUX PREMIUM 91 PREMIUM 91 DIESEL <br /> Product REGULAR REGULAR PREMIUM PREMIUM Biodiesel <br /> Product Line 1 1 1 2 1 <br /> Tested From 2 18 2 18 8 <br /> Existing/New Existing Existing Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No. U.R. U.R. U.R. U.R. U.R. <br /> Pump Operating Pressure(psi) 40.00 40.00 40.00 32.00 34.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 3.00 3.00 <br /> Holding PSI <br /> NIA for Electronic Lo's <br /> Resiliency(ml) <br /> NIA for Electronic Lo's <br /> Metering PSI <br /> NIA for Electronic Lo's <br /> Opening Time(sec) <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass Pass Pass <br /> Technician Comments:TESTED Q2 AND Q6 ON DISPN. 1/2 FOR REG.AND PREM.TESTED Q1 AND Q5 ON DISPN. <br /> 17/18 FOR REG AUX AND PREM.AUX TESTED Q3 ON DISPN.8 FOR DSL <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2023 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />