Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> H&S ENERGY PRODUCTS, LLC 3084 1 3940 N TRACY BLVD,TRACY April 19, 2023 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The float and chain in the 10/11A, 11/12A, 14/15A failed to stop the flow of product at the <br /> dispenser when tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The service technician adjusted the float and chain and verified functionality. <br /> This is a Class II violation. <br /> 327 CCR 2638(a), 2641 Q)Leak detection equipment not installed/calibrated/operated/maintained per manufacturer <br /> instructions. <br /> OBSERVATION: The 208 sensor in the 91 STP was not not properly programmed. The sensor was programmed to <br /> L10 however, L10 is no longer in use. Technician reprogrammed the 91 STP sensor from L10 to L1. <br /> REGULATION GUIDANCE:All monitoring equipment shall be installed, calibrated, operated, and maintained in <br /> accordance with manufacturer's instructions, and certified for operability, proper operating condition, and proper <br /> calibration. Immediately contact a properly licensed and certified contractor to ensure all sensors are properly <br /> programmed. <br /> CORRECTIVE ACTION: Ensure that all leak detection equipment is properly programmed and maintained at all <br /> times. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> On site for a routine monitoring system certification. All violation was corrected on site. No additional follow-up <br /> are needed. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($156). To schedule an appointment, please call (209)468-3420. <br /> FA0008057 PR0507837 SCO01 04/19/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />