Laserfiche WebLink
(E� <br /> JONES COVEY GROUP, IINC- <br /> D E VE LO P E RS/CONSTRUCTORS <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot Flying J 617 LodiM DATE: 04-11-2023 <br /> State Facility# CONTACT: Site Manager <br /> 15237 N. Thorton Road, Lodi Ca 95242 PHONE: 209-339-4066 <br /> JOB#: 2363349-1-1 <br /> Tank # T-2 87 T-4 87 T-5 91 <br /> Product 87 87 91 <br /> LD Manufacturer VMI Fe-Petro Fe-Petro <br /> LD Model LD-3000 STP MLD-HC STP MLD-HC <br /> Sump Condition Good Good Good <br /> Operation Pressure 38 PSI 38 PSI 33 PSI <br /> (PSI) <br /> Opening Time(Sec) 22 Sec. 14 Sec. 10 Sec. <br /> Metering Pressure 18 PSI 18 PSI 19 PSI <br /> (PSI) <br /> Functional Element 30 PSI 30 PSI 30 PSI <br /> Holding Pressure <br /> Leak Rate LD Detected 3 GPH 3 GPH 3 GPH <br /> (GPH) <br /> Does LD Detect 3 GPH Yes Yes Yes <br /> Leak Rate? <br /> LD Serial 00309024 01060046 01060076 <br /> Comments: <br /> Technician Keith Henderson License Number VMI - 5104/3248 <br /> Signature G "464�m, <br /> 9595 Lucas Ranch Rd.# 100 Rancho Cucamonga, CA 91730 <br /> Office (909)972-7S81 Fax (909) 484-0300 Fax California State License#804431 A,B,HAZ <br />