Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> COUNTRY MART GAS&FOOD 34243 S CHRISMAN RD, TRACY March 15, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the UDC 1/2, 7/8, and 5/6. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed 1.5 cup of liquid from the UDC 1/2, 7/8, and 5/6. Ensure <br /> that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 4/14/2023 . <br /> Documents provided during inspection: <br /> - blank Certificate of Financial Responsibility form <br /> - blank Letter from Chief Financial Officer <br /> - list of free CUPA Classes <br /> CERS assistance was provided during the inspection today. The Financial Responsibility documents were <br /> uploaded into CERS during the inspection today. Inspection report will be mailed to facility per request of owner. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($156). To schedule an appointment, please call (209)468-3420. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: March 15, 2023 Inspector: Inspector Phone: <br /> Printed Name and Title: KRISTINA SAETERN, EH Specialist (209)616-3045 <br /> Emailed to Taranjit Sandhu, Owner <br /> FA0003290 PR0231801 SCO01 03/15/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />