Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-91-PS 1-Diesel-PS 1-87-FRS <br /> Sump Manufacturer XERXES XERXES XERXES XERXES <br /> Sump Depth (inches) 64 1/2" 64" 64" 64" <br /> Sump Bottom to Top of 17" 16" 17" 12" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:17 10:22 10:27 9:22 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:47 10:52 10:57 9:52 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID 2-91-FRS 3-Diesel-FRS UDC 1&2 UDC 3&4 <br /> Sump Manufacturer XERXES XERXES Bendell Corp Bendell Corp <br /> Sump Depth (inches) 64" 64" 31" 31" <br /> Sump Bottom to Top of 12" 12" 8" 8 1/2" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:32 9:27 9:42 9:37 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:02 9:57 10:12 10:07 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />