Laserfiche WebLink
SAN JOARU <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />CAGASOLINE INC <br />2115 W YOSEMITE AVE, MANTECA <br />March 28, 2023 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />319 <br />CCR 2635, 2637.2, 2665, 2712 Failure to comply with overfill prevention equipment requirements. <br />OBSERVATION: The 87, 91 and diesel tanks do not have an approve overfill prevention system. <br />REGULATION GUIDANCE: All underground storage tanks shall be equipped with an overfill prevention system that <br />does not allow for manual override and meets one of the following requirements: <br />1. Alert the transfer operator when the tank is 90 percent full by restricting the flow into the tank or triggering an <br />audible and visual alarm; or <br />2. Restrict delivery of flow to the tank at least 30 minutes before the tank overfills, provided the restriction occurs <br />when the tank is filled to no more than 95 percent of capacity; and activate an audible alarm at least five minutes <br />before the tank overfills; or <br />3. Provide positive shut-off of flow to the tank when the tank is filled to no more than 95 percent of capacity; or, <br />4. Provide positive shut-off of flow to the tank so that none of the fittings located on the top of the tank are <br />exposed to product due to overfilling. <br />CORRECTIVE ACTION: Immediately contact a properly licensed, trained, and certified contractor to install an <br />approved overfill prevention system. Replacement of a mechanical flapper valve requires a permit and inspection <br />by the EHD. If an external audio/visual alarm is replaced, provide a copy of the service receipt to the EHD. If an <br />approved overfill prevention system can't be installed immediately, there is a possibility that the 87, 91 and diesel <br />UST system may be red tagged to prevent fuel inputs. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 04/27/2023 . <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in -office CERS help will be provided at EHD hourly rate <br />($156). To schedule an appointment, please call (209) 468-3420. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />Received by: Date: March 28, 2023 <br />Inspector: <br />Inspector Phone: <br />Printed Name and Title: <br />PAUL NSO, EH Specialist <br />(209) 616-3049 <br />E mail report to: Gurpreet Sandhu, Environmental Contact. <br />FA0017819 PR0526335 SCO01 03/28/2023 <br />EHD 23-01 Rev. 12/06/2021 Page 6 of 6 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />