Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS-M 2-87-PS-S 3-91-PS <br /> Sump Manufacturer CSI CSI CSI <br /> Sump Depth (inches) 33" 32" 33" <br /> Sump Bottom to Top of 18" 15" 14" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:42 11:47 11:52 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 12:12 12:17 12:22 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UCD 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 35" 35" 32" 35" <br /> Sump Bottom to Top of 21" 19" 17" 16" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:57 12:02 12:37 12:42 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 12:27 12:32 1:07 1:12 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />