Laserfiche WebLink
<br />www.teaminc.com <br /> <br />STI SP001 Tank Inspection <br />Report <br />Community Fuels <br />Tank no. T-611 <br />March 30th 2019 Stockton, CA <br />Page 8 of 26 <br /> <br /> <br /> <br />TANK CONFIGURATION TANK HAS <br />CRDM? <br />TANK HAS <br />SPILL <br />CONTROL? <br />AST CATEGORY <br />Single wall AST in contact <br />with ground <br />No No 3 <br />Single wall AST in contact <br />with ground <br />No Yes 2 <br />Elevated tank Yes Yes 1 <br />AST with RPB Yes Yes 1 <br />AST with double-bottom Yes Yes 1 <br />Double-wall AST with overfill <br />prevention <br />Yes Yes 1 <br />Double-wall AST without <br />overfill prevention <br />Yes No 3 <br />Vertical tank resting on <br />concrete (conforms with <br />definition of RPB) <br />Yes Yes 1 <br />Vertical tank resting on <br />concrete (conforms with <br />definition of RPB) <br />Yes No 3 <br /> <br /> <br />AST Type and Size (U.S. <br />gallons) <br />Category 1 Category 2 Category 3 <br />Shop –Fabricated AST’s <br />0 – 1100 <br />(0-4161 liters) <br />P  P  P, E&L (10)  <br />1101 – 5000 <br />(4168-18,927 <br />liters) <br />P  P, E&L (10)  [P, E&L (5), I <br />(10)]  <br />Or <br />[P, L(2), E (5)] <br /> <br />5,001 – 30,000 <br />(18,931-113,562 <br />liters) <br />P, E(20)  [P, E(10), I(20)] <br /> <br />Or <br />[P, E(5), L (10)] <br /> <br />[P, E&L (5), I <br />(10)]  <br />Or <br />[P, L(1), E (5)] <br /> <br />30,001-50,000 <br />(113,566- <br />189,271 liters) <br />P, E(20)  P, E&L (5), I (15) <br /> <br />P,E&L (5), I (10) <br /> <br />Portable Containers P  P  P  *** <br /> <br />