Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> 0 Check this box if tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> Do not complete this section if either box is checked. <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and ❑ ❑ ❑ <br /> termination; and 2 tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup ❑ ❑ ❑ <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑ ❑ ❑ <br /> Was accuracy of system's water level readings tested? ❑ ❑ ❑ <br /> Were all probes reinstalled properly? ❑ ❑ ❑ <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑ I ❑ ❑ <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> 9. COMMENTS <br /> Describe all answers marked "No"or "Fail"and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> UPON ARRIVAL SITE SHOWING 3 ACTIVE ALARMS. <br /> L - 2 DISP 3 / 4 LOW LIQUID - NO BRINE IN RESERVOIR <br /> L - 3 DISP 5 / 6 LOW LIQUID - BRINE AT BOTTOM OF RESERVOIR - ALARMED THIS MORNING <br /> T 7:58 AM <br /> S - 11 NO VACUUM - DURING TESTING FOUND S - 11 ACTUALLY HAS VACUUM, THIS MEANS <br /> VACUUM SWITCH IS BAD. ALARM WAS NEVER ABLE TO BE CLEARED. <br /> ALSO OPENED 87 FILL SUMP AND 91 FILL SUMP, BOTH 208 SENSORS WERE LIFTED OFF <br /> BOTTOM OF SUMP , REMOVED 15 GALLONS OF WATER DURING TESTING. AFTER <br /> COMPLETION ALL SENSORS RETURNED TO BOTTOM OF SUMPS AND IN SLEEVES. <br /> T TIME OF DEPARTURE THREE ACTIVE ALARMS REMAIN, SITE WILL NEED TO HIRE <br /> CONSTRUCTION / MAINTENANCE CREW FOR REPAIRS TO SUMP AND REPLACEMENT OF <br /> SENSOR. <br /> Page 5 of 6 <br />