Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2360191 Date: 6/14/2023 <br /> Site Name/ID. Chevron 212470/212470 <br /> Address: 3400 N MacArthur Drive <br /> City: Tracy State: CA Zip: 95376 <br /> Tank ID 87 91 dsl <br /> Product REG UNLEAD PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 1 1 1 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No. U.R. U.R. U.R. <br /> Pump Operating Pressure(psi) 50.00 50.00 45.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI <br /> NIA for Electronic Lo's <br /> Resiliency(ml) <br /> NIA for Electronic Lo's <br /> Metering PSI <br /> NIA for Electronic Lo's <br /> Opening Time(sec) <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: /1-1 Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2023 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />