The following is an itemized list of underground storage tank violations that have not <br /> been addressed for EMI LS LIQUOR & SPORTS SHOP* as of December 27, 2023. <br /> Open violations from May 08, 2023 inspection <br /> Violation#208-Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports.The incorrect and missing information included the following from the inspection reports: <br /> -Several DO reports do not have the printed name of the UST owner/operator. <br /> -Two DO reports do not include a response from the Owner/Operator on Section 6. <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#306-Failure to remove,analyze, and properly dispose of water in secondary containment <br /> (pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the diesel STP sump. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed 2.5 gallons of liquid from the diesel STP sump. Ensure <br /> that all sumps and annular spaces are maintained free of liquid. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#308-Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The 91 BRAVO float and chain in the 1/2 UDC failed to stop the flow of product at the dispenser <br /> when tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 91 UST system may be red tagged to prevent fuel inputs. <br /> Page 3 of 4 <br />