Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Nella Oil#427 3300 Waterloo Rd, Stockton December 06, 2023 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 202 CCR 2712(i) Failure to retain a paper or electronic copy of the permit to operate at the facility. <br /> OBSERVATION:A current copy of the UST operating permit was not found on site. The most recent permit on site <br /> was the 2022 operating permit. <br /> REGULATION GUIDANCE:A copy of the UST operating permit and all attachments and conditions shall be <br /> retained at the facility. <br /> CORRECTIVE ACTION:A copy of the 2023 operating permit was obtained during the inspection.This was <br /> corrected on site. <br /> This is a repeat violation, Class II. <br /> 203 CCR 2712(b)(1-2)Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> -The 5/2/2023 Secondary Containment Test report was not found on site. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance <br /> records; (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION:A copy of the 5/3/2023 Secondary Containment Test was obtained during the inspection. <br /> This was corrected on site. <br /> This is a repeat violation, Class Il. <br /> Overall Inspection Comments: <br /> All violations were corrected on site. No additional follow up is required. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($162). To schedule an appointment, please call (209)468-3420. <br /> Documents provided: list of free CUPA classes <br /> FA0003600 PR0231765 SCO01 12/06/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />