Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> NATIONAL PETROLEUM MANTECA 2072 W YOSEMITE AVE, MANTECA September 05, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> 1. OBSERVATION: Liquid was observed in the racine fuel 110 STP sump. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed approximately one liter of liquid from the racine fuel 110 <br /> STP sump. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> -------------------------------------------------------------------------------------------------------------------------------- <br /> 2.OBSERVATION: Liquid was observed in the UDC#9. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: Immediately remove this liquid, make a hazardous waste determination per Title 22 <br /> hazardous waste regulations, and manage it accordingly. Ensure that all sumps and annular spaces are maintained <br /> free of liquid. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 10/05/2023 . <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($162). To schedule an appointment, please call (209)468-3420. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: September 05, 2023 Inspector: Inspector Phone: <br /> Printed Name and Title: PAUL NSO, EH Specialist (209)616-3049 <br /> E mail report to: Nick Patel, Environmental Contact. <br /> FA0004625 PR0231426 SCO01 09/05/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 7 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />